Configuring the Remote LCDs (RDCs)
Following are the steps that need to be followed to configure the remote LCD units.
Select
“Edit”.
Select
“Manual
Pgm”.
Use “Cmor”
and select
“RS-485
NW”.
Select
“RDC
Annciatrs”.
Enter a “1” in the
map to enable the
RDC at the
selected address.
Installing the DACT
Following are the steps that need to be followed to install the DACT.
Select
“Edit”.
Select
“Manual
Pgm”.
Select
“Outputs”.
Use
“Cmor”
and select
“Option
Mods”.
Select “DACT CFG”. Follow the screen
prompts to set up the
DACT.
These are the parameters that need to be set when installing the DACT.
Test Time
The time that the DACT will regularly call in to the central station to check the
connection.
Select the
line number
The DACT can connect to two lines. Select which one is to be configured.
Select the
dialing method
The DACT can dial using pulse or tone. Select which is needed.
Configuring the DACT Accounts
Following are the steps that need to be followed to configure the remote LED units.
Select
“Edit”.
Select
“Manual
Pgm”.
Select
“Outputs”.
Use “Cmor”
and select
“Option Mods”.
Select “DACT
ACCTS”.
Follow the screen
prompts to set up the
DACT Accounts.
The following information is set up for the two possible DACT accounts
Format
This is the format that is used to report to the Central station. The options are
SIADCS8, SIADCS20, ADEMCO, 4/2-1400, 3/1-1400, 3/1-2300, 4/2-2300.
Number of
attempts
This is the number of times that the DACT will attempt to dial the account before
trying the next account.
Must report
event type
When selected yes, the DACT must report these events to the selected account. If
not selected the DACT will only report to one account.
Account
number
The number to identify the account at the central station.
CIC prefix
The prefix used by the DACT to dial through a PBX to access a line.
Phone
number
The phone number which the DACT will dial for this account.
Setting System Timers
Following are the steps to set system timers.
Select
“Edit”.
Select
“Manual
Pgm”.
Use “Cmor”
and select
“Sys
Params”.
Use
“Cmor”
and select
“Timers”.
Use “Cmor” to
select the timers to
be set.
Summary of Contents for MPC-6000
Page 2: ......
Page 39: ......
Page 40: ...FARADAY 8 Fernwood Road Florham Park New Jersey 07932 P N 315 049403FA 1...