M P C 6 0 0 0 / 7 0 0 0 P R O G R A M M I N G M A N U A L
10
The programming model of the system
The following diagram shows the programming model of the MPC-6000 and
MPC-7000 systems.
22
1
32
12
T
T
T
T
Input group
Output Zones
up to 255
An input group can
activate any or all
Output Zones.
NACs and Audible
bases can connect to
one and only one output Zone.
Input devices
can belong to
one local input
group.
Monitor modules and detector
base relays can connect to one
and only one output zone.
Remote relays and remote
LEDs connect to output zones.
Each input device can be
configured for type of
operation, i.e.,
alarm, manual pull,
waterflow, sil waterflow,
trouble, supervisory, non-
fire, panel reset, alarm
silence, acknowledge.
Each relay can
have its output
behavior
configured, i.e.,
non-silencable,
trouble active,
supervisory, pre-
alarm, silenceable,
trouble silence,
supervisory
silence.
Each LED and remote
relay can have its
output behavior
configured, i.e.,
Alarm active, trouble,
supervisory, pre-alarm.
GC
GC
GC
GC
GC
The input group may
be configured for
different activation, i.e.,
none, fire zone, cross
zone, PAS, pre signal,
wildcard.
Each output can be set
for the control behavior,
i.e., non-silencable,
trouble active,
supervisory, pre-alarm,
silenceable, trouble
silence, supervisory
silence.
The MPC 6000 and 7000 programming model
Can set various
behaviors depending on
the type of system
zone. (Mainly output
coding.)
System groups: general alarm
drill
recall
alert
trouble
quick test
up to 240 input
groups