M P C 6 0 0 0 / 7 0 0 0 P R O G R A M M I N G M A N U A L
12
Monitor Modules with relay and single input
Parameter
Description
Label
Generic label identifying the detector by loop number and address.
Led off
LED will be defaulted to ON.
Input Usage
Input usage will be set to alarm.
Input Group
Inputs will be set to input group 241.
Network Group
This will not be set and will need to be set manually. (Future use)
Output Type
Will be set to non-silenceable.
Output Zone
Will be set to 1.
Intelligent LEDs
Parameter
Description
Label
Generic label identifying the detector by loop number and address.
Output Type
Will be set to non-silenceable.
Output Zone
Will be set to 1.
NACs
Parameter
Description
Notification
Device Type
Set to Audible.
Output Type
Will be set to silenceable.
Output Zone
Will be set to 1.
System Parameter
Parameter
Description
Label
Set to “FARADAY AUTO Prgrmd”
Drill Enable
ON
Auto Silence Timer
Off
Alarm Silence Inhibit
Off
Panel Reset Inhibit
Off
Auto Alarm silence
Off
Trouble Reminder
12 hours
NAC sound time
5 seconds
Quick test exit
30 minutes
City Tie Activation
Not changed
Global Commands
Not changed
Printer ESC
Not changed
•
Presence of LCD Annunciators are detected and programmed as installed when
detected.