M P C 6 0 0 0 / 7 0 0 0 P R O G R A M M I N G M A N U A L
28
Below is a list of the timers and their functions:
Parameter
Description
Alarm Silence Inhibit
The period of time that the alarm will sound before it can be
silenced.
Panel Reset Inhibit
The period of time that the panel is prevented from being
reset after an alarm is annunciated.
Trouble Reminder
The time period before a trouble will come back to remind
the installer.
Quick test NAC time
The length of time that the NACs will sound in Quickest.
Quick test exit
The time that Quick test will exit automatically after
inactivity.
Configuring the City Tie Activation
The City Tie, once installed, may be activated by a trouble, a supervisory or both.
Select
“Edit”.
Select
“Manual
Pgm”.
Use “Cmor”
and select
“Sys
Params”.
Select
“CityTrbActvn”.
Use the screen to
select which
activation is
required and press
“Bsav”.
Setting Trouble Ack Required
Troubles and supervisory events are normally self-restoring; however, if it is required
that they need to be acknowledged before clearing, follow the procedure below:
Select
“Edit”.
Select
“Manual
Pgm”.
Use “Cmor”
and select
“Sys
Params”.
Select “Trb
Ack Req”.
Press 1 for yes
and then press
“Bsav”.
Setting the System Reporting Type
Depending on the type of system configured, the panel will report power failure in
different periods of time. (No reporting for Auxiliary, 6 hours for Central Station and
15 hours for Remote Station)
Select
“Edit”.
Select
“Manual
Pgm”.
Use “Cmor”
and select
“Sys
Params”.
Select
“System
Type”.
Use the screen to
select which
system type is
required and press
“Bsav”.
Copying the Primary to the Backup
Once the primary configuration has been checked out and is running correctly it is a
good idea to copy the configuration into the backup. This is accomplished as follows:
Select
“Edit”.
Select
“Copy
Primary”.
Select
“Cyes” to
start the
copy.
The screen will indicate the copy is
in progress. It will take several
minutes.