page 5-51
Programming
QFE
FD8420 issue02_F
9. With
Map To
on the top line of the display press the
button once until
Bit Number
is
displayed.
10. Press
Enter
once to select
Bit Number
.
11. Press the
Optimise
button four times so that the cursor moves to bit 4.
12. Press the
button once to change the bit state of bit 4 to zero (0).
13. Press the
Optimise
button three times so the cursor moves to bit 7.
14. Press the
button once to change the bit state of bit 7 to one (1).
15. Press
Enter
once to accept the change. The display will flash once to confirm the
change has been accepted.
16. Press
#
once to return to
Bit Number
.
17. With
Bit Number
on the top line of the display press the
button once until
Polarity
is displayed on the top line.
18. Press
Enter
once to select
Polarity
.
19. With
Positive logic
displayed press
Enter
once to change to
Inverse logic
.
The display will flash once to confirm the change has been accepted.
20. Press
#
four times to return to
Stopped and ready
.
Please remember to keep the above settings they must be permanently saved. See section
5.4.5
10
9
11
12
13
14
15
16
x 1
#
17
x 1
18
19
19
19
20
20
Summary of Contents for QFE Series
Page 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Page 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Page 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Page 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Page 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Page 73: ...QFE page 3 25 Applications FD841405_F...
Page 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Page 181: ...Modbus page 6 4 5MC FD510007...