page 5-21
Programming
QFE
FD8420 issue02_F
5.3.6
Permanent Store Menu
Save Param
-
This item saves all the parameter settings to a permanent
store. This means that if the control supply is removed from the main control board, the
parameters will still remain stored and will be recalled the next time the unit boots up. See
section
5.4.5
.
Power on Param
-
This item recalls all the parameter settings from the last
Save Param
and loads the current parameters with these recalled values.
Default Params
-
This item loads all the parameters with their factory default
values. The
Starting
parameter is set to
Remote
by this menu item, (
P51
, bit 7).
5.3.8
The Inputs Menu
Digital i/p 1
-
This menu item gives access to the programming
parameters for the first programmable input (see section
2.5.3
of Electrical Installation). A
worked example showing how to program a digital input is given in section
5.5.4
.
Digital i/p 2
(QFE+)
-
This menu item gives access to the programming
parameters for the second programmable input (see section
2.5.4
of Electrical Installation).
A worked example showing how to program a digital input is given in section
5.5.6
.
Digital i/p 3
(QFE+)
-
This menu item gives access to the programming
parameters for the third programmable input (see section
2.5.4
of Electrical Installation). A
worked example showing how to program a digital input is given in section
5.5.5
.
Temperature i/p
-
This menu item gives access the heatsink temperature
in ºC from a suitable temperature sensor (fitted at the factory). It is also possible to set the
heatsink temperature above which the unit will not start, set via the Set Level submenu. This
temperature sensor is not fitted as standard ( normally a thermal switch is fitted) so this
menu item will not normally not be of any use to the customer.
4 - 20mA i/p
(QFE+)
-
This menu item gives access to the programming
parameters for the 4 - 20mA input (see section
2.5.4
of Electrical Installation). A worked
example showing how to program the 4 - 20mA input is given in section
5.5.8
.
DC Input
(QFE+)
-
This menu item gives access to the programming
parameters for the DC input (section
2.5.4
of Electrical Installation). A worked example
showing how to program the DC input is given in section
5.5.9
.
5.3.7
The Password Menu
Enter Password
-
This option enables the user to unlock a unit by entering
previously set password. When the unit is
locked
the user can read all parameters as
usual, but the user cannot write to any parameters. The unit
can
be started and stopped
whilst it is locked. The default setting is for the unit to have no password set, (see section
5.4.10
).
Change Password
-
This option enables the user to change a previously set
password, to enter a password for the first time, or to clear the password. This last action is
performed by changing the password to zero (0) and pressing
Enter.
This action clears
any set password, but the control supply must be cycled or the unit reset by pressing the
and
buttons at the same time, after the password has been cleared (see section
5.4.9
).
Summary of Contents for QFE Series
Page 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Page 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Page 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Page 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Page 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Page 73: ...QFE page 3 25 Applications FD841405_F...
Page 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Page 181: ...Modbus page 6 4 5MC FD510007...