21
02/09/2003
Commissioning 2
If the softstart trips on overload during the start, check starter is large enough for the load.
No :
Date :
Subject :
24
02/09/2003
"Too Hot"
Check ventilation into the cabinet. If the unit has worked for a long time check fans and airflow
through unit.
No :
Date :
Subject :
Wiring
Category
2
24/06/2002
When replacing star delta starters
If you are planning to re use the existing overload and contactor, ensure they are sized for the full
motor line current and not just for delta phase current.
No :
Date :
Subject :
8
09/09/2002
Running inside the DELTA 1
The unit must be set to firing mode 1. The current displayed is now the phase current (58% of the
line current).
No :
Date :
Subject :
11
11/09/2002
Running inside the DELTA 2
When running with firing mode 1 the maximum cable length between the starter and the motor is
reduced to 50M.
No :
Date :
Subject :
14
02/09/2003
Running inside the DELTA 3
When running in the delta an inline contactor must be used.
No :
Date :
Subject :
03 September 2003
Page 3 of 3
Summary of Contents for QFE Series
Page 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Page 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Page 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Page 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Page 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Page 73: ...QFE page 3 25 Applications FD841405_F...
Page 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Page 181: ...Modbus page 6 4 5MC FD510007...