Programming
page 5-20
QFE
FD8420 issue02_F
Figure 5.3.5d Overload Trip Graph
Notes
1.
Delay = ‘Overload Delay’.
Overload Level
-
This parameter holds the level in Amps at which an
Overload
trip will start integrating (see the graph below). The default value for this parameter
is 1.1
×
Unit Full Load Current, but is expressed in Amps.
Special case:
if a load current
exceeding 7.2 x FLC occurs for longer than 60 mS, a
Shearpin Trip
is forced whenever
the
Overload
is
On
, see section
5.3.11
.
Overload Delay
-
This parameter holds an arbitrary dimensionless number
which slows down the integration of an
Overload
trip. The larger the value of the number
stored here, the longer a given
Overload
will take to result in a trip. The default value of
this parameter is 140.
0.01
0.1
1
10
100
1000
1
2
3
4
5
6
7
8
9 10
Fault current ( Motor Current x N )
Seconds
to trip
Overload start point
Delay = 80
Delay = 30
Delay = 10
(Default)
Delay = 140
7.2 x FLC Shearpin Cutoff
Summary of Contents for QFE Series
Page 18: ...Mechanical Installation QFE page 1 2 FD841205_F...
Page 26: ...Mechanical Installation QFE page 1 10 FD841205_F...
Page 43: ...QFE page 2 19 Electrical Installation FD8413 issue03_F...
Page 50: ...Electrical Installation QFE page 2 26 FD8413 issue03_F...
Page 51: ...QFE Soft Start Motor Controller Technical Data for the QFE and QFEplus Applications...
Page 73: ...QFE page 3 25 Applications FD841405_F...
Page 158: ...page 5 47 Programming QFE FD8420 issue02_F This page is left intentionally blank...
Page 181: ...Modbus page 6 4 5MC FD510007...