Channel list edition 1 for EP104 version 4.08
Load guard and motor settings
No.
Name
Range
Factory
Setting
S
C200 Load guard function
0 – 4
3
0
Disabled Service and troubleshooting only
1
Reverse when closing, stop when opening
2
Stop when closing and reverse when opening
3
Reverse when closing and opening
4
Stop when closing and opening
S
C202 Type of power supply
0 - 5
0
0
3x400 V with neutral
1
3x230 V without neutral
2
1x230 V with neutral, asymmetric
3
3x400 V without neutral (see separate instructions)
4
1x230 V with neutral, Frequency converter (see separate instructions DB409)
5
1x230 V with neutral, symmetric
S
C205 Load guard for personal protection active during the
closing movement. Superior to C200.
0-1
1
0
Disabled
1
Active
S
C211 Load guard delay
0.01-2.50 seconds
0.06
S
C212 Load guard, connection delay on start, all starts
0.1-2.5 seconds
1.0
S
C221 Motor protection delay
3.0-5.0 seconds
5.0
S
C230
AB
Set motor power readout for personal protection,
motor 1
0.00 and 0.12-0.35 kW 0.20
C231
B
Motor power readout, motor 1
0.00-1.99 kW
S
C232
B
Set load guard limit for motor 1 opening
0.05-1.99 kW
0.70
S
C233
B
Set load guard limit for motor 1 closing
0.05-1.99 kW
0.70
S
C240
AC
Set motor power readout for personal protection,
motor 2
0.00 and 0.12-0.35 kW 0.20
C241
C
Motor power readout, motor 2
0.00-1.99 kW
S
C242
C
Set load guard limit for motor 2 opening
0.05-1.99 kW
0.70
S
C243
C
Set load guard limit for motor 2 closing
0.05-1.99 kW
0.70
C251
B
Motor current readout, motor 1
0.0-20.0A
S
C252
B
Set motor current readout, motor 1 opening
0.0 and 0.5-6.0A
0,8
S
C253
B
Set motor current readout, motor 1 closing
0.0 and 0.5-6.0A
0,8
C261
C
Motor current readout, motor 2
0.0-20.0A
S
C262
C
Set motor current readout, motor 2 opening
0.0 and 0.5-6.0A
0,8
S
C263
C
Set motor current readout, motor 2 closing
0.0 and 0.5-6.0A
0,8
C271
AB
Power factor readout motor 1
0.00-0.99 cos
φ
C281
AC
Power factor readout motor 2
0.00-0.99 cos
φ
A = Not displayed when C202 = 4, B = Not displayed when L001 = 0, C = Not displayed when L002 = 0