15

ENGLISH

05

When this function is activated, the 

OPEN command

 during opening will stop movement. 

If parameter 

06

 is 

no

 the system is ready for opening. 

If parameter 

06

 is 

Y

 the system is ready for closing.

Y

 = when opening it stops

no

 = disabled

06

When this function is activated, the 

OPEN command

 during opening reverses movement. 

If parameters 

05

 and 

06

 are 

no

 OPEN will have no effect during opening.

Y

 = when opening it reverses

no

 = disabled

07

When this function is activated, the 

OPEN command

 during pause stops operation.

If parameters 

07

 and 

08

 are 

no

 OPEN resets the pause time

Y

 = when in pause it stops

no

 = disabled

08

When this function is activated, the 

OPEN command

 during pause causes closing. 

If parameters 

07

 and 

08

 are 

no

 OPEN resets the pause time.

Y

 

= when in pause it closes

no

 = disabled

09

When this function is activated, the 

OPEN command

 during closing stops operation, 

otherwise it reverses movement.

Y

 = stops

no

 = reverses

10

Activation of DEAD-MAN closing (command always pressed). Releasing the 

CLOSE 

command

 will stop operation

Y

 

= active

no

 = disabled

11

When this function is activated, the 

CLOSE command

 has priority over OPEN,  otherwise 

OPEN has priority over CLOSE.

Y

 = active

no

 = disabled

12

When this function is activated, the 

CLOSE command

 commands closing when released. 

As long as CLOSE is activated, the unit stays in closing pre-fl ashing.

Y

 = closes when released

no

 = closes immediately

13

When this function is activated, the 

CLOSE command

 during opening stops operation, 

otherwise the CLOSE command commands reverse immediately or when opening is com-
pleted (see also parameter 

14

)

Y

 

= CLOSE stops

no

 = CLOSE reverses

14

When this function is activated, and if parameter 

13

 is 

no

, the 

CLOSE command

 commands 

immediate closing at the end of the opening cycle (stores CLOSE). If parameters 

13

 and 

14

 

are 

no

 CLOSE commands immediate closing.

Y

 = closes at the end of 

        opening

no

 = immediate closing

15

When this function is activated, with the system blocked by a STOP, a 

next OPEN

 

moves in the opposite direction. If parameter 

15

 is 

no

 it always closes.

Y

 = moves in the opposite 

        direction

no

 = always closes

16

When this function is activated, during closing, the 

CLOSING SAFETIES

 stop and allow 

motion to resume when they are disengaged, otherwise they immediately reverse opening.

Y

 = closes when disengaged

no

 = immediate reverse

17

When this function is activated, the 

CLOSING SAFETIES

 command closing when they are 

disengaged (see also parameter 

18

).

Y

 = closing when FSW 

is disengaged

no

 = disabled

18

When this function is activated, and if parameter 

17

 is 

Y

, the unit will wait for the 

opening cycle to end before executing the closing command provided by the 

CLOSING SAFETIES

.

Y

 = closes at the end of 

        opening

no

 = disabled

19

When this function is activated, during closing, 

LOOP2

 stops and allows motion to resume 

when it is disengaged, otherwise it immediately reverses opening.

Y

 = closes when disengaged

no

 = immediate reverse

20

When this function is activated, 

LOOP2

 commands closing when it is disengaged (see also 

parameter 

21

). 

Y

 = closes if LOOP2 is clear

no

 = disabled

21

When this function is activated, and if parameter 

20

 

is

 

Y

, the unit will wait for the opening 

cycle to end before executing the closing command provided by 

LOOP2.

Y

 = closes at the end of 

        opening

no

 = disabled

22

When this function is activated: in case of a blackout, once electrical power has been 
restored, if an OPEN command is not active the automated system recloses immediately.

Y

 = active

no

 = disabled

23

LOOP 1

 commands opening and, once completed, it closes if disengaged (useful in case 

of vehicle backing-up with consecutive loops). If disabled, when LOOP 1 is disengaged, it 
does not close.

Y

 = closes if LOOP1 clear

no

 = disabled

24

When this function is activated, an open or close command is only carried out after 
the safeties have been disengaged.

Y

 = active

no

 = disabled

25

A.D.M.A.P. function

When this function is activated, the result is operation of 

safeties compliant with French 

regulations.

Y

 = active

no

 = disabled

26

When this function is activated, the 

CLOSING SAFETIES

 during closing stop and reverse 

movement when they are disengaged, otherwise they reverse immediately.

Y

 = stops and reverses when 

disengaged.

no

 = reverses immediately.

27

DO NOT CHANGE

no

28

DO NOT CHANGE

no

29

DO NOT CHANGE

no

30

When this function is activated, the 

LOOP1

 commands are prioritised rather than the 

LOOP2

 commands.

Y

 = active

no

 = disabled

Summary of Contents for B680

Page 1: ...B680H...

Page 2: ......

Page 3: ...NNECTIONS 7 4 1 Terminal board J1 inputs 7 4 2 Terminal board J2 outputs 8 4 3 Terminal board J3 external flashing lamp 8 4 4 Terminal board J4 loop detector 8 4 5 Connector J5 Motor 8 4 6 Connector J...

Page 4: ...AAC declines all liability as concerns safety and efficient operation of the automated system if system components not produced by FAAC are used 19 For maintenance strictly use original parts by FAAC...

Page 5: ...e covering compartment is the same for both models while the bar dimensions differ as shown in detail at bar S and bar L Fig 8 4 INSTALLING THE AUTOMATED SYSTEM 4 1 Preliminary checks For the safety a...

Page 6: ...rrectly operate the barrier pointing out the areas of potential danger 6 MANUAL OPERATION Should manual operation of the barrier be required due to electrical power cut offs or automated system ineffi...

Page 7: ...photocell The barrier is equipped with a lateral covering profile fitted in the compartment opening under which there are holes for containing Safebeam BUS or wireless photocells To install the photoc...

Page 8: ...re upgrade J15 Integrated flashing traffic light connector SW1 Programming key F SW2 Programming key SW3 Programming key SW4 SW5 LOOP 1 LOOP 2 calibration button M1 M1A M2 Optional module connector Co...

Page 9: ...P and GND Fig 26 EMR Emergency contact N C terminal 7 means any device e g switch which if activated in a situation of emergency will open the barrier until the contact is restored When activated this...

Page 10: ...24 25 for OPENING LOOP 2 magnetic loop LOOP 2 SAFETY CLOSE terminals 26 27 for SAFETY CLOSING 4 5 Connector J5 Motor Rapid connector for connecting the motor 4 6 Connector J7 Encoder The B680H barrie...

Page 11: ...details on MASTER SLAVE configuration refer to section 9 MA bu BUS accessories menu For functions associated with this parameter see paragraph 5 3 no Display Function Default LO Operating logics A Aut...

Page 12: ...NG movement to then display 01 once the position of gate OPEN is reached Example of a status sequence displayed starting from a closed barrier The sequence does not include statuses 09 and 10 which co...

Page 13: ...status of the segments of the left hand digit must correspond to the automated system at rest and without pulse generators or or safeties engaged When the CLOSE photocells are engaged the bottom segme...

Page 14: ...mum power 40 FC Closing motor power Adjusts the thrust of the motor during the closing phase 00 Minimum power 50 Maximum power 40 PF Pre flashing This parameter is used to activate the flashing lamp f...

Page 15: ...used together with n C to verify the use of the system and for use of Service Request 00 nC Cycle programming in hundreds of thousands Is used to set a countdown of the system operation cycles the val...

Page 16: ...t have double insulation Make a preferably square or rectangular loop by preparing a PVC cable duct or by tracing the paving as shown in figure 16 the corners must be cut at a 45 angle to avoid cable...

Page 17: ...lways closes 16 When this function is activated during closing the CLOSING SAFETIES stop and allow motion to resume when they are disengaged otherwise they immediately reverse opening Y closes when di...

Page 18: ...value Read only parameter F1 Loop 1 frequency selection This parameter lets you set an oscillation frequency specific to the loop connected to the Loop 1 input or lets the system choose the most adeq...

Page 19: ...is value increases or decreases the output voltage for OUT 5 changing the brightness of the rope light 04 St STATUS OF THE AUTOMATED SYSTEM Exit from programming storage of data and automated system s...

Page 20: ...display the indicationshowntothesideconfirming the fact that there are no engaged photocells or active pulse generators 7 2 Setup Before being put into operation the E680 board requires a setup proced...

Page 21: ...tion systems to the fully closed position with the Mt parameter of the Base configuration level or by operating the release device as indicated in sections 6 and 7 on page 4 3 Access Base programming...

Page 22: ...03 04 05 06 dF Y Y Y Y Y Y Ct MA MA MA MA MA MA bu no no no no no no So 10 10 10 10 10 10 Sc 10 05 05 04 02 02 S1 05 05 05 05 05 05 S2 05 05 05 05 05 05 Advanced Configuration cF 01 02 03 04 05 06 FO...

Page 23: ...eted no effect closes immediately after opening is completed OPEN IN PAUSE resets pause time closes blocks operation closes resets pause time closes when disengaged WHEN CLOSING immediately reverses t...

Page 24: ...ly after opening is completed blocks operation no effect no effect closes immediately after opening is completed OPEN IN PAUSE resets pause time closes blocks operation resets pause time closing inhib...

Page 25: ...time immediately reverses to opening immediately reverses to opening BLOCKED opens and closes after the pause time closes no effect opening and closing inhibited no effect closing inhibited opens and...

Page 26: ...hts Foot 2 3 3 4 4 5 6 6 Foot 2 3 3 4 4 4 5 6 Skirt 2 3 3 4 4 5 6 Skirt Foot 3 3 3 4 4 5 Table 3 12 BALANCING TABLES The following two tables indicate the fixing position of the pistons on the rocker...

Page 27: ...5 5 5 5 6 6 Skirt 4 5 5 5 5 6 6 Skirt Foot 5 5 5 5 5 6 Table 5 13 DEFAULT SELECTION TABLES cF parameter The purpose of the two following tables is to determine depending on the length of the bar and...

Page 28: ...1 5 m m 2 3 X 1 5mm 2 230V 6 6 2 3 4 2 1 1100 mm 900 mm 470 mm 436 m m 280 m m Fig 5 Fig 5 Raccolta immagini Pictures collection Collection d images Photo Kollection Conjunto de imagenes Afbeeldingen...

Page 29: ...27 DX SX Fig 10 Fig 10 Fig 11 Fig 11 M M L1 L2 L3 L1 L2 L3 Fig 12 Fig 12 Fig 13 Fig 13 Fig 14 Fig 14 Fig 15 Fig 15 Fig 16 Fig 16...

Page 30: ...28 Fig 17 Fig 17 L...

Page 31: ...29 Fig 18 Fig 18 Fig 19 Fig 19 1 2 Fig 20 Fig 20...

Page 32: ...30 Fig 21 Fig 21...

Page 33: ...8 9 10 11 SAFE TX CL RX CL 1 2 5 4 3 1 2 12 13 14 15 16 17 18 19 20 21 24 24 24 24 OUT1 OUT2 OUT3 GND Relais NO COM J2 Fig 24 Fig 24 J1 24 GND 24 GND OPEN CLOSE FSW STOP ALARM GND 24 3 4 5 6 7 8 9 10...

Page 34: ...32 DS1 DL1 DL2 BUS BUS RX TX DL2 DS1 ON ON BUS BUS DS1 DL1 DL2 BUS BUS DL2 DS1 ON ON BUS BUS 2EASY 1 2 J6 Fig 28 Fig 28 Fig 27 Fig 27 Fig 29 Fig 29 Fig 30 Fig 30...

Page 35: ...33 Fig 31 Fig 31...

Page 36: ...34 Fig 32 Fig 32...

Page 37: ...B680H Guida per l utente User s guide Instructions pour l utilisateur Anleitungen f r den Benutzer Gu a para el usuario Gebruikersgids...

Page 38: ...anovra prima di inserire il sistema di blocco togliere alimentazione all impianto chiave di sblocco triangolare standard ruotare la chiave in senso orario fino all arresto ed estrarla Fig 18 rif a chi...

Page 39: ...1 Die Firma FAAC lehnt jede Haftung f r Sch den ab die durch unsachgem en oder nicht bestimmungsgem en Gebrauch derAutomatik verursacht werden 2 Die Firma FAAC bernimmt keine Haftung im Falle von nich...

Page 40: ...YSTEEMB680H 1 WAARSCHUWINGEN 1 FAAC aanvaardt geen enkele aansprakelijkheid voor schade die ontstaat uit oneigenlijk gebruik of ander gebruik dan waarvoor het automatische systeem is bedoeld 2 FAACisn...

Page 41: ...5 1 2 Fig 18...

Page 42: ...732719 Rev FAAC S p A Soc Unipersonale Via Calari 10 40069 Zola Predosa BOLOGNA ITALY Tel 39 051 61724 Fax 39 051 758518 www faac it www faacgroup com...

Reviews: