HOLD CLOSE / HOLD OPEN function
When this function is activated, the automated system will monitor the position of the beam
at set intervals (see parameter
A1
). If the beam is not completely closed or completely open
(depending on the logical condition of the board), the automated system will command a
CLOSE or OPEN movement to bring the beam back to the correct position, for a maximum
of 3 seconds. If, when the 3 seconds have elapsed, the bar does not go back to completely
closed/open position (e.g. because the bar is blocked), the function will be disabled until the
next OPEN command is received.
Y
A1
HOLD CLOSE / HOLD OPEN function activation time
This parameter indicates the time interval between two activations of the HOLD OPEN /
HOLD CLOSE function, expressed in minutes. (from
00
to
99
)
60
r1
Loop 1 frequency reading
This menu item lets you verify the reading of the current oscillation frequency of the loop
connected to the Loop 1 input. The indication should be read as follows:
First digit: tens (kHz)
Second digit: units (kHz)
Decimal point: hundreds (kHz)
For example, the reading
05.
refers to a reading of 105 kHz
Read-only parameter
r2
Loop 2 frequency reading
This menu item lets you verify the reading of the current oscillation frequency of the loop
connected to the Loop 2 input. (see parameter
r1
for explanations on how to read the
indicated value)
Read-only parameter
F1
Loop 1 frequency selection
This parameter lets you set an oscillation frequency specific to the loop connected to the
Loop 1 input, or lets the system choose the most adequate setting among the 4 available.
A
Automatic
selection
1-2-3-4
Frequency 1-2-3-4
Note:
When you exit the Advanced configuration menu after having changed the loop
operation frequency setting, the system will be recalibrated. This will provide an updated
frequency reading once you re-enter the menu to consult the values of parameters
r1
or
r2
A
F2
Loop 2 frequency selection
This parameter lets you set an oscillation frequency specific to the loop connected to the
Loop 2 input, or lets the system choose the most adequate setting among the 4 available.
A
Automatic
selection
1-2-3-4
Frequency 1-2-3-4
Note:
When you exit the Advanced configuration menu after having changed the loop
operation frequency setting, the system will be recalibrated. This will provide an updated
frequency reading once you re-enter the menu to consult the values of parameters
r1
or
r2
A
h1
LOOP 1 holding time
Is used to set presence time on loop 1. When this time has elapsed, the board will self-
calibrate and signal “loop clear” (LED DL3 off). When the board is turned on, an automatic
reset is carried out.
Y
5
minutes
no
infi nite
no
h2
LOOP 2 holding time
Is used to set presence time on loop 2. When this time has elapsed, the board will self-
calibrate and signal “loop clear” (LED DL4 off). When the board is turned on, an automatic
reset is carried out.
Y
5
minutes
no
infi nite
no