background image

10

FAAC MODEL 950 BM Door Operator

5.4.7 MICROSWITCH No. 10 -  RS232 PORT

It makes it possible to enable the RS232 port connection to PC for 

software update. In normal use conditions, the dip switch is in OFF 

position.

 

OFF = Port DISABLED

 

ON = Port ENABLED

6. 950 I/O ELECTRONIC CONTROL UNIT

 

(Fig. 10)

6.1 LAYOUT AND DESCRIPTION

 

DS1

 Function

 OFF

 ON

1

 Push and Go pause time

 2 seconds

 Automatic

2

Opening delay with electric 

lock

 200ms

 500ms

MICROSWITCH No. 1 -  Push and go Pause time

Following the opening with the Push & Go function you can choose: 

to have the automated system use a fixed 2 seconds pause time,

or the time used by opening with the pulse generator in automatic

operating mode (see chap. 10.7 - Diagram 3: Setup).

 

 

OFF = 2 sec. pause time

 

 

ON = Automatic pause time

     MICROSWITCH No. 2 -  

Lock activation delay

  

If this dip-switch is ON (enabled), the door movement is delayed by 

500msec with respect to the electric lock command. If OFF (disabled), 

delay is 200 msec. 

SW1       SET-UP pushbutton 

            Hold down the SET-UP button for 5 sec. to start the set-up  cycle.

  1

  FUSE F1 

   T4A 125 Vac. - 5x20 (UL/CSA)

  2

 

J1 CONNECTOR

 Transformer Secondary winding - fig. 10   

  3

 

J2 CONNECTOR

 Rapid Connector of Manual/Night, Open, 

Automatic function selector switch

  4

 

J3  CONNECTOR

  KP-Controller Connection

1- 2 Connector of KP-Controller programming unit (optional) as 

shown in fig. 24.

 

Use a 2 x 0.5 mm² shielded cable (“bus” communication) for the 

connection. Respect the connection polarity as  shown in figure 

24.

 

Important: The maximum permissible length of the connection 

cable is 150’.

To inhibit operation of the SD-KEEPER, make the jumper between 

terminals of the LOCK switch (fig.24).

  5

 

J4  TERMINAL BLOCK

 Inputs Connection (figs. 11,12,16)

7- 8 GND

 

Accessories power supply Negative and contacts Common

9 +24Vdc

 

+24Vdc accessories power supply

10  Internal Command - N.O. Contact

 

Any pulse generator (pushbutton, sensor, etc.) which, by closing 

a contact, commands door opening. 

To install several pulse generators as Internal Command, connect 

the N.O. contacts in parallel.

 

11  External Command - N.O. Contact

 

Any pulse generator (pushbutton, sensor, etc.) which, by closing 

a contact, commands door opening. 

To install several pulse generators as External Command, connect 

the N.O. contacts in parallel.

12  Emergency Command - N.C. Contact

 

Any pulse generator (normally a pushbutton) which, by opening 

a contact, commands an emergency closure of the system. 

Alternatively this input can be used to command emergency 

opening by programming the system in a suitable manner using 

the KP-CONTROLLER programming unit (optional).

To install several emergency command devices, connect the N.C. 

contacts in series.

 

NOTE: If emergency command devices are not connected, jumper 

inputs 7 and 12.

 

Attention: Using the KP-CONTROLLER programming unit, you 

can change the type of contact from N.C. to N.O.

13  CLOSE Safety Command - N.C. Contact

 

Any device (safety sensor, photocell, etc.) which, by opening a 

contact, has a safety effect on the closing movement of the door.

 

The safety device causes an immediate reversing of the closing 

movement of the door, but has no effect on the opening movement 

of the door. 

 

To install several CLOSE safety devices, connect the N.C. contacts 

in series.

 

N.B.: If the CLOSE safety devices are not installed, jumper inputs 

7 and 14.

 7   8    9   10  11 12  13  14  15  16  17  18  19

GND

GND

+ 24 Vdc

Internal Command

External Command

Closure Safety Command

ST

OP

 Safety Command

Emergency Command

Key Command

Fire-alarm Command

Card Reader Command

GND

GND

J4

Fig. 11

 7   8    9   

 13  14  15  

TX

RX

PB SENSOR

+

-

C

+

+

-

-

C

J4

Fig. 12

 7   8    9   10  11 12  13  14 15  16  17  18 19

(800) 878-7829

www.FastGateOpeners.com

Summary of Contents for 950 BM

Page 1: ...950 BM Swing Door Operator 800 878 7829 www FastGateOpeners com...

Page 2: ...2 FAAC MODEL 950 BM Door Operator shielded Fig 2a Fig 3 1 1 2 2 Fig 4 Fig 4b Fig 4a 3 1 4 1 4 3 2 2 6 5 5 8 8 7 800 878 7829 www FastGateOpeners com...

Page 3: ...3 FAAC MODEL 950 BM Door Operator Fig 5 Fig 6 800 878 7829 www FastGateOpeners com...

Page 4: ...he operator and the arm is required add the optional modular extensions Each modular extension increases the standard height of 1 1 8 inches It is not rccommended to use more than 2 extensions TABLE A...

Page 5: ...ween the operator and the arm is required add the optional modular extensions Each modular extension increases the standard height of 1 1 8 inches It is not rccommended to use more than 2 extensions T...

Page 6: ...24 Vdc with encoder Dimensions 20 3 4 x 4 1 8 x 4 3 4 length x height x depth Weight 22 lbs Operating ambient temperature 4 to 131 F Protection class IP 23 internal use only Dimensions and leaf max we...

Page 7: ...tor mounting position must not exhibit any significant deformation The operator must be mounted parallel to the floor NOTE Iftheslidingarmistobeused thedriving armmustbemounted before the operator is...

Page 8: ...d down SW1 button for at least 5 sec until the LD2 red LED on the 950MPS board lights up The LED will start flashing to indicate that SET UP process is in progress During this process the following pa...

Page 9: ...y obstacle e g side wall is prevented which would cause interruption of the work cycle 5 4 6 MICROSWITCH No 8 SCP Function SCP Function Selectable Close Power If the SCP function is enabled the door c...

Page 10: ...GND Accessories power supply Negative and contacts Common 9 24Vdc 24Vdc accessories power supply 10 Internal Command N O Contact Any pulse generator pushbutton sensor etc which by closing a contact c...

Page 11: ...h by closing a contact commands door closing Permanence of the closed contact inhibits operation of any other pulse generator To install several devices as FIRE ALARM Command connect the N O contacts...

Page 12: ...e side of the cover fig 4 ref 2 The selector switch position is fixed however depending on the type of installation on doorpost or on lintel the connection cable to the 950I O unit must be positioned...

Page 13: ...closing direction until the next fixing position of the stop point screw fig 21 ref 5 is in line with the inspection slot and fix the screw again 5 Reinstall the arm correctly see par 3 3 6 Run a new...

Page 14: ...x0 5mm max 50m cable Fig 24 If the two LOCK terminals are connected to each other as shown in Fig 24 all keys on the programmer are disabled 10 3 DIAGNOSTICS The KP Controller also without display has...

Page 15: ...ernal radars are disabled The Key command causes opening and closing after the night pause time elapses standard 7 sec Adjusting range of night pause time from 0 to 30 sec To obtain partial opening in...

Page 16: ...to select sub menu or parameter and confirm with the OK key An asterisk on the display indicates the currently active setting To exit programming select the exit function at each level Other wise afte...

Page 17: ...agram 3 Setup Diagram 4 Lock SETUP 80 7 SEC 2 SEC CLOSING STANDARD NO STANDARD OBSTACLE DETECTION NIGHT PAUSE TIME PARTIAL OPENING PAUSE TIME EXIT LOCK OFF ON ALWAYS ONE WAY NIGHT NIGHT KIT LOCK EXIT...

Page 18: ...NOSTICS NR CYCLE XXXX ALARM N alarm description PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 KEEP SETTINGS OFF ON 8 8 EXIT ADVANCED MENU OPERATION PARAMETERS CLOSING SPEED OPENING SPEED cor...

Page 19: ...ASSWORD 0000 PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 IN OUT SETUP EMERG OPEN CLOSE OUT OP CL NO OUT ALARM NO NC USCITA NC NO NC ADVANCED MENU OPERATION PARAMETERS VARIOUS EXIT CHANGE PASSWORD correc...

Page 20: ...SETUP STAND SETUP STANDARD NO STANDARD INTERLOCK MASTER SLAVE NO MEMORY WITH MEMORY EXIT NEW PASSWORD 0000 NEW PASSWORD 0000 NEW PASSWORD 0000 NEW PASSWORD 0000 MASTER SLAVE ON OFF ON OFF 2 LEAVES TES...

Page 21: ...UN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2 FUN 0 00 00 TIME BAND 5 FUN 0 00 00 TIME BAND 4 FUN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2 FUN 0 00...

Page 22: ...if the cause of signalled malfunction was removed it restores normal operation 5 ADVANCED MENU PASSWORD To access the advanced menu insert the 4 digit password default 0000 1 OPERATION PARAMETERS Dia...

Page 23: ...o 5 different time bands for each day of the week by setting the band starting time and assign an operational function to each time band When the KP Controller s internal clock reaches the starting ti...

Page 24: ...se totally in order to activate the sensor of the second door 6 Door B opens Fig 28 Door A Door B 7 The person exits 8 Door B closes after the night pause time elapses The operation is identical if th...

Page 25: ...ately reversed The partial opening function enables control of total opening of the master only The operating functions must be set on the master automated system only or on the KP Controller if conne...

Page 26: ...Check that LED 5 6 7 are ON These LED s show safety and stop circuits Refer to page 6 installing jumpers for more information Door will not open 1 Check that LED 5 6 7 are ON These LED s show safety...

Page 27: ...en subject to misuse neg ligence or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or...

Reviews: