FAAC MODEL 950 BM Door Operator

5.4. PROGRAMMING THE MICROSWITCHES (fig.9)

The 950BM has two series of microswitches, one on the 950MPS board 

and one on the 950 I/O board.

The system is supplied with all the microswitches in the OFF position.

5.4.3. MICROSWITCH No. 3 - SELECTOR FUNCTION  

This function allows the operating function to be selected with the 

selector switch in the “2” position.

 

OFF = MANUAL Function

 

ON = NIGHT Function

 

5.4.4. MICROSWITCH No. 4 - PUSH AND GO

 

When activated, this function enables the opening command to be 

given by pushing the closed door manually. It is sufficient to give the 

door an initial push/pull in the opening direction.

 

OFF = Function DISABLED

 

ON = Function ENABLED

WARNING: It is advisable not to enable this function if the door is 

subject to strong wind, according to its structure and dimensions, as this 

could activate the system’s spontaneous opening or motion reversing.

5.4.5 . MICROSWITCHES Nos. 5/6//9 - INACTIVE

5.4.6. MICROSWITCH No. 7 -  STOP SAFETY DEVICE

It makes it possible to detect activation of the STOP safety device 

during the entire door travel (COMPLETE) or to disable detection 

beyond 70° opening (REDUCED).

 

OFF = COMPLETE Function

 

ON = REDUCED Function

When the STOP safety control is ensured by an active sensor fitted 

on the leaf, if you enable the REDUCED function, the detection of any 

obstacle (e.g. side wall) is prevented  which would cause interruption 

of the work cycle. 

5.4.6. MICROSWITCH No. 8 -  S

CP Function

SCP Function (Selectable Close Power)

If the SCP function is enabled, the door can be closed even if

there is friction due to rigid seals or electric locks with a particularly

difficult connection. When the SCP function is operating, the electronic 

anti-crush facility is still active, but is less sensitive. For reasons of safety, 

we therefore advise you to use the function only in case of real need.

 

 

OFF = Function DISABLED

 

 

ON = Function ENABLED

6. 950 I/O ELECTRONIC CONTROL UNIT LAYOUT

5.4.1. MICROSWITCH No. 1 - CLOSING STROKE

 

This function enables the closed position force to be increased by 

further loading the transmission system after the door has reached 

the mechanical closure stop.

It is advisable to use this function to assist activation of the electric lock.

 

OFF = Function DISABLED

 

ON = Function ENABLED

5.4.2. MICROSWITCH No. 2 - SET-UP PROCESS

When mounting the “sliding” arm or for opening angles greater than 

90°, this microswitch has to be enabled.

 

OFF = Function DISABLED

 

ON = Function ENABLED

     MICROSWITCHES 

OFF

ON

Fig. 9

Fig. 10

N°  Function

 OFF

 ON

1

Closing stroke

 Disabled

 Enabled

2

Setup process

 Standard

 Non-standard

3

Outside selector - pos. 2

 Manual

 Night

4

Push And Go

 Disabled

 Enabled

5

Not in use

 -

 -

6

Not in use

 -

 -

7

Safety STOP detection

 Complete

 Reduced

8

SCP

 Disabled

 Enabled

9

Not in use

 -

 -

10

 RS232 Port

 Disabled

 Enabled

Tab. 8: DS1 on the 950MPS board

1

2

3

4

5

6

7

8

9 10

(800) 878-7829

www.FastGateOpeners.com

Summary of Contents for 950 BM

Page 1: ...950 BM Swing Door Operator 800 878 7829 www FastGateOpeners com...

Page 2: ...2 FAAC MODEL 950 BM Door Operator shielded Fig 2a Fig 3 1 1 2 2 Fig 4 Fig 4b Fig 4a 3 1 4 1 4 3 2 2 6 5 5 8 8 7 800 878 7829 www FastGateOpeners com...

Page 3: ...3 FAAC MODEL 950 BM Door Operator Fig 5 Fig 6 800 878 7829 www FastGateOpeners com...

Page 4: ...he operator and the arm is required add the optional modular extensions Each modular extension increases the standard height of 1 1 8 inches It is not rccommended to use more than 2 extensions TABLE A...

Page 5: ...ween the operator and the arm is required add the optional modular extensions Each modular extension increases the standard height of 1 1 8 inches It is not rccommended to use more than 2 extensions T...

Page 6: ...24 Vdc with encoder Dimensions 20 3 4 x 4 1 8 x 4 3 4 length x height x depth Weight 22 lbs Operating ambient temperature 4 to 131 F Protection class IP 23 internal use only Dimensions and leaf max we...

Page 7: ...tor mounting position must not exhibit any significant deformation The operator must be mounted parallel to the floor NOTE Iftheslidingarmistobeused thedriving armmustbemounted before the operator is...

Page 8: ...d down SW1 button for at least 5 sec until the LD2 red LED on the 950MPS board lights up The LED will start flashing to indicate that SET UP process is in progress During this process the following pa...

Page 9: ...y obstacle e g side wall is prevented which would cause interruption of the work cycle 5 4 6 MICROSWITCH No 8 SCP Function SCP Function Selectable Close Power If the SCP function is enabled the door c...

Page 10: ...GND Accessories power supply Negative and contacts Common 9 24Vdc 24Vdc accessories power supply 10 Internal Command N O Contact Any pulse generator pushbutton sensor etc which by closing a contact c...

Page 11: ...h by closing a contact commands door closing Permanence of the closed contact inhibits operation of any other pulse generator To install several devices as FIRE ALARM Command connect the N O contacts...

Page 12: ...e side of the cover fig 4 ref 2 The selector switch position is fixed however depending on the type of installation on doorpost or on lintel the connection cable to the 950I O unit must be positioned...

Page 13: ...closing direction until the next fixing position of the stop point screw fig 21 ref 5 is in line with the inspection slot and fix the screw again 5 Reinstall the arm correctly see par 3 3 6 Run a new...

Page 14: ...x0 5mm max 50m cable Fig 24 If the two LOCK terminals are connected to each other as shown in Fig 24 all keys on the programmer are disabled 10 3 DIAGNOSTICS The KP Controller also without display has...

Page 15: ...ernal radars are disabled The Key command causes opening and closing after the night pause time elapses standard 7 sec Adjusting range of night pause time from 0 to 30 sec To obtain partial opening in...

Page 16: ...to select sub menu or parameter and confirm with the OK key An asterisk on the display indicates the currently active setting To exit programming select the exit function at each level Other wise afte...

Page 17: ...agram 3 Setup Diagram 4 Lock SETUP 80 7 SEC 2 SEC CLOSING STANDARD NO STANDARD OBSTACLE DETECTION NIGHT PAUSE TIME PARTIAL OPENING PAUSE TIME EXIT LOCK OFF ON ALWAYS ONE WAY NIGHT NIGHT KIT LOCK EXIT...

Page 18: ...NOSTICS NR CYCLE XXXX ALARM N alarm description PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 KEEP SETTINGS OFF ON 8 8 EXIT ADVANCED MENU OPERATION PARAMETERS CLOSING SPEED OPENING SPEED cor...

Page 19: ...ASSWORD 0000 PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 IN OUT SETUP EMERG OPEN CLOSE OUT OP CL NO OUT ALARM NO NC USCITA NC NO NC ADVANCED MENU OPERATION PARAMETERS VARIOUS EXIT CHANGE PASSWORD correc...

Page 20: ...SETUP STAND SETUP STANDARD NO STANDARD INTERLOCK MASTER SLAVE NO MEMORY WITH MEMORY EXIT NEW PASSWORD 0000 NEW PASSWORD 0000 NEW PASSWORD 0000 NEW PASSWORD 0000 MASTER SLAVE ON OFF ON OFF 2 LEAVES TES...

Page 21: ...UN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2 FUN 0 00 00 TIME BAND 5 FUN 0 00 00 TIME BAND 4 FUN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2 FUN 0 00...

Page 22: ...if the cause of signalled malfunction was removed it restores normal operation 5 ADVANCED MENU PASSWORD To access the advanced menu insert the 4 digit password default 0000 1 OPERATION PARAMETERS Dia...

Page 23: ...o 5 different time bands for each day of the week by setting the band starting time and assign an operational function to each time band When the KP Controller s internal clock reaches the starting ti...

Page 24: ...se totally in order to activate the sensor of the second door 6 Door B opens Fig 28 Door A Door B 7 The person exits 8 Door B closes after the night pause time elapses The operation is identical if th...

Page 25: ...ately reversed The partial opening function enables control of total opening of the master only The operating functions must be set on the master automated system only or on the KP Controller if conne...

Page 26: ...Check that LED 5 6 7 are ON These LED s show safety and stop circuits Refer to page 6 installing jumpers for more information Door will not open 1 Check that LED 5 6 7 are ON These LED s show safety...

Page 27: ...en subject to misuse neg ligence or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or...

Reviews: