background image

8

FAAC MODEL 950 BM Door Operator

4. START-UP

 

1)  Make the electrical connections to the 950 I/O electronic control 

unit as described in paragraph 6, and connect the mains power 

supply to the specific terminal (fig.1-ref.10) ensuring to crimp the 

earth wire to the lug (fig.1-ref.12) screwed to the support profile 

(fig.1-ref.2). Then tighten the terminal (fig.1-ref.13)

 

To gain access to the control unit, pass the cables through the 

special conduit (fig.1-ref.1) or break the knockout areas on the 

casing sides (fig.4-ref.6).

IMPORTANT: When mounting the sliding arm or for opening angles 

greater than 90°, turn microswitch no. 2 to ON before connecting 

power to the system.
2)  Close the door.

3)  Power up the operator.

4)  Check that the green LEDs LD1 and LD3 on the board 950MPS 

light up.

5)  Check that  the status signalling LEDs on the board 950I/O are 

in the default status shown in Table 7 .

NOTE: The default status of the LEDs with the door closed at rest is 

shown in bold type.

Table 7: Operation of the  status signalling LEDs for 950 I/O board

LED

ON

OFF

LD1

Accessories power present

Accessories power absent

LD2

Card Reader active

Card Reader inactive

LD3

Internal sensor active

Internal sensor inactive

LD4

External sensor active

External sensor inactive

LD5

Emergency inactive

Emergency active

LD6

STOP safety device inactive

STOP safety device active

LD7

CL safety device inactive

CL safety device active

LD8

Key active

Key inactive

LD9

Fire-alarm active

Fire-alarm active

6)     Run a SET-UP cycle as indicated in paragraph 4.1. 

4.1. SET UP PROCESS

Once the system is powered up, hold down SW1 button for at least 

5 sec., until the LD2 red LED on the 950MPS board lights up. The 

LED will start flashing to indicate that SET UP process is in progress. 

During this process the following parameters are set:

-  measuring the mass of the door;

-  determining the travel stop positions;

The door opens at low speed, then closes half way before switching 

back to opening.

Subsequent closure is performed by the return spring.

The process may be inhibited in any of the following conditions:

-  function selector switch in the 2 (MANUAL/NIGHT) position or KP-

CONTROLLER programming unit in MANUAL or NIGHT position. 

-  incorrect connection of the accessories (electric lock, control/safety 

devices);

-  incorrect positioning of the programming unit microswitches.

NOTE: To repeat the initialisation procedure hold down the SW1 button 

for more than 5 seconds.

Check that door opens and closes correctly by sending an opening 

command to one of the following inputs: Internal Sensor, External 

Sensor or Key command. Set the trimmers (par.5.2) and program the 

microswitches (par.5.4) according requirements. 

5.  950 MPS ELECTRONIC CONTROL UNIT (Fig. 8)

5.1 SETTING THE TRIMMERS

The programming unit features trimmers (fig.8) which regulate the 

following parameters:

Trimmer TR1

 to set the opening speed.

Setting from 4 to 10 seconds.

Trimmer TR2

 to set the closing speed.

Setting from 4 to 10 seconds.

Trimmer TR3 

to set the pause time (AUTOMATIC logic).

Setting from 0 to 30 seconds.

5.2 SIGNALLING LEDs

LD1 Led

 = Green LED - electric motor power supply.

LD2 Led

 = Red LED - indicates SET-UP/Alarm.

LD3 Led

 = Green LED - 5V power supply.

950MPS ELECTRONIC CONTROL UNIT 

LAYOUT AND DESCRIPTION

MICROSWITCHES

RS-232 CONNECTOR

ADJUSTING TRIMMER 

SIGNALLING LED

MOTOR CONNEC-

TOR

40VDC CONNEC-

TOR 

Fig. 8

(800) 878-7829

www.FastGateOpeners.com

Summary of Contents for 950 BM

Page 1: ...950 BM Swing Door Operator 800 878 7829 www FastGateOpeners com...

Page 2: ...2 FAAC MODEL 950 BM Door Operator shielded Fig 2a Fig 3 1 1 2 2 Fig 4 Fig 4b Fig 4a 3 1 4 1 4 3 2 2 6 5 5 8 8 7 800 878 7829 www FastGateOpeners com...

Page 3: ...3 FAAC MODEL 950 BM Door Operator Fig 5 Fig 6 800 878 7829 www FastGateOpeners com...

Page 4: ...he operator and the arm is required add the optional modular extensions Each modular extension increases the standard height of 1 1 8 inches It is not rccommended to use more than 2 extensions TABLE A...

Page 5: ...ween the operator and the arm is required add the optional modular extensions Each modular extension increases the standard height of 1 1 8 inches It is not rccommended to use more than 2 extensions T...

Page 6: ...24 Vdc with encoder Dimensions 20 3 4 x 4 1 8 x 4 3 4 length x height x depth Weight 22 lbs Operating ambient temperature 4 to 131 F Protection class IP 23 internal use only Dimensions and leaf max we...

Page 7: ...tor mounting position must not exhibit any significant deformation The operator must be mounted parallel to the floor NOTE Iftheslidingarmistobeused thedriving armmustbemounted before the operator is...

Page 8: ...d down SW1 button for at least 5 sec until the LD2 red LED on the 950MPS board lights up The LED will start flashing to indicate that SET UP process is in progress During this process the following pa...

Page 9: ...y obstacle e g side wall is prevented which would cause interruption of the work cycle 5 4 6 MICROSWITCH No 8 SCP Function SCP Function Selectable Close Power If the SCP function is enabled the door c...

Page 10: ...GND Accessories power supply Negative and contacts Common 9 24Vdc 24Vdc accessories power supply 10 Internal Command N O Contact Any pulse generator pushbutton sensor etc which by closing a contact c...

Page 11: ...h by closing a contact commands door closing Permanence of the closed contact inhibits operation of any other pulse generator To install several devices as FIRE ALARM Command connect the N O contacts...

Page 12: ...e side of the cover fig 4 ref 2 The selector switch position is fixed however depending on the type of installation on doorpost or on lintel the connection cable to the 950I O unit must be positioned...

Page 13: ...closing direction until the next fixing position of the stop point screw fig 21 ref 5 is in line with the inspection slot and fix the screw again 5 Reinstall the arm correctly see par 3 3 6 Run a new...

Page 14: ...x0 5mm max 50m cable Fig 24 If the two LOCK terminals are connected to each other as shown in Fig 24 all keys on the programmer are disabled 10 3 DIAGNOSTICS The KP Controller also without display has...

Page 15: ...ernal radars are disabled The Key command causes opening and closing after the night pause time elapses standard 7 sec Adjusting range of night pause time from 0 to 30 sec To obtain partial opening in...

Page 16: ...to select sub menu or parameter and confirm with the OK key An asterisk on the display indicates the currently active setting To exit programming select the exit function at each level Other wise afte...

Page 17: ...agram 3 Setup Diagram 4 Lock SETUP 80 7 SEC 2 SEC CLOSING STANDARD NO STANDARD OBSTACLE DETECTION NIGHT PAUSE TIME PARTIAL OPENING PAUSE TIME EXIT LOCK OFF ON ALWAYS ONE WAY NIGHT NIGHT KIT LOCK EXIT...

Page 18: ...NOSTICS NR CYCLE XXXX ALARM N alarm description PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 KEEP SETTINGS OFF ON 8 8 EXIT ADVANCED MENU OPERATION PARAMETERS CLOSING SPEED OPENING SPEED cor...

Page 19: ...ASSWORD 0000 PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 IN OUT SETUP EMERG OPEN CLOSE OUT OP CL NO OUT ALARM NO NC USCITA NC NO NC ADVANCED MENU OPERATION PARAMETERS VARIOUS EXIT CHANGE PASSWORD correc...

Page 20: ...SETUP STAND SETUP STANDARD NO STANDARD INTERLOCK MASTER SLAVE NO MEMORY WITH MEMORY EXIT NEW PASSWORD 0000 NEW PASSWORD 0000 NEW PASSWORD 0000 NEW PASSWORD 0000 MASTER SLAVE ON OFF ON OFF 2 LEAVES TES...

Page 21: ...UN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2 FUN 0 00 00 TIME BAND 5 FUN 0 00 00 TIME BAND 4 FUN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2 FUN 0 00...

Page 22: ...if the cause of signalled malfunction was removed it restores normal operation 5 ADVANCED MENU PASSWORD To access the advanced menu insert the 4 digit password default 0000 1 OPERATION PARAMETERS Dia...

Page 23: ...o 5 different time bands for each day of the week by setting the band starting time and assign an operational function to each time band When the KP Controller s internal clock reaches the starting ti...

Page 24: ...se totally in order to activate the sensor of the second door 6 Door B opens Fig 28 Door A Door B 7 The person exits 8 Door B closes after the night pause time elapses The operation is identical if th...

Page 25: ...ately reversed The partial opening function enables control of total opening of the master only The operating functions must be set on the master automated system only or on the KP Controller if conne...

Page 26: ...Check that LED 5 6 7 are ON These LED s show safety and stop circuits Refer to page 6 installing jumpers for more information Door will not open 1 Check that LED 5 6 7 are ON These LED s show safety...

Page 27: ...en subject to misuse neg ligence or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or...

Reviews: