background image

2

ON

1    2     3    4

Terminal

Description

Device connected

1

OPEN

Device with NO contact. 
(chap. FUNCTION LOGICS)

2

FSW

Device with NC contact.
shuts down automated system 

3

STOP

Device with NC contact.
shuts down automated system 

4

- 24Vdc

Power supply to accessories 

5

+ 24Vdc

6

FAIL 

SAFE

Negative controlled for photocells 
(see fail safe function)

7

C

Motor common contact 

8

OP

Motor Opening stage

9

CL

Motor Closure stage

10 11

LAMP

Flashing lamp output
230Vac max 60W

DESCRIPTION OF TERMINAL-BOARDS

6. FUNCTION 

LOGICS

Status

Open

(pulse)

Stop

Safe(FSW)

Closed

Opens and closes 

after pause time 

Disables

Open and Close

/

Opening

/

Blocks

/

Open

Recharges  
pause time

Blocks

Recharges  
pause time

Closure

Opens

Blocks

Opens

Blocked

Opens

Disables

Open and Close

Inhibits
closure

A AUTOMATIC Logic

1.

OPEN command

.

   Any pulse generator with NO contact which opens the gate

when activated. In EP logic, it also commands closure.

2.

FSW safety devices and/or other safety devices.

   All devices, such as photocells or sensitive edges etc with 

an NC contact - if they are activated, they generate an 
opening or shut-down of the automated system according to 
programming.

3.

STOP command.

      Any NC pulse generator, which commands instant shut down of 

the automated system until a new OPEN command is given.

4.

 FAIL SAFE.

    When using this terminal for connecting the negative wire 

to power the transmitters and photocells, you can use the 
FAILSAFE function. If this function is enabled, the unit 
verifi es the operation of the photocells before every closing 
cycle.

If you do not intend connecting any device to 

terminals 2 and 3, you must jumper connect them 
to terminal 4.

DESCRIPTION OF INPUTS

EP SEMI-AUTOMATIC Logic  

Status

Open

(pulse)

Stop

Safe(FSW)

Closed

Opens

/

/

Opening

/

Blocks

/

Open

CLOSES

Blocks

Blocks

Closure

Opens

Blocks

Opens

Blocked

Opens/closes

/

/

The automatic or semi-automatic function logic can be selected 
with the SW2 microswitch, as shown in fi g. 3.

8. MAINTENANCE

The 200MPS control board does not require any special periodic 
controls. In the event of faults, it is important to control the fuses 
and the status LEDs.

The function logic and the relevant functions can be selected by 
confi guring the 

DS1

 microswitches group as per table below.

5. LOGIC AND FUNCTIONS PROGRAMMING 

ON

OFF

SW1

ACTIVE 5 sec

INACTIVE

FLASHING LAMP 

PRE-FLASHING

SW2

Logic A

Logic EP

FUNCTION

LOGICS 

SW3

Reopens 

immediately

Reopens when 

disengaged

SAFETY DEVICES 

TRIPPED

SW4

FSW control 

active

FSW control 

inactive

FAIL SAFE

7.  AUTOMATED SYSTEM TEST

When you have fi nished programming, check if the system is 
operating correctly. In particular, check if the safety devices are 
operating correctly.

Pause time adjustment 

Pause time can be adjusted with trimmer TR1, varying the 
pause from 0 to 60 secs. Turn the trimmer clockwise to increase 
time.

4. CONNECTIONS

Fig. 2

M

1

2

5

4

3

1

2

RX CL1

TX CL1

230Vac

J1

J4

OP FSW STOP

-

+ -TXFSW

COM

OP

CL

LAMP

N

L

7

8

9

10

11

12

13

Other safety 
device

FAAC

200MPS

230V
Max60W

1

2

3

4

5

6

Summary of Contents for 200MPS

Page 1: ...200MPS...

Page 2: ......

Page 3: ...73 23 CEE e successiva modi ca 93 68 CEE 89 336 CEE e successiva modi ca 92 31 CEE e 93 68 CEE Nota aggiuntiva Questo prodotto stato sottoposto a test in una con gurazione tipica omogenea tutti prodo...

Page 4: ...l automazione no a nuovo comando di OPEN 4 FAIL SAFE Utilizzando questo morsetto per il collegamento del negativo dell alimentazione dei trasmettitori fotocellule si pu utiliz zare la funzione FAILSAF...

Page 5: ...nt amendments 92 31 EEC and 93 68 EEC Additional note This product underwent tests in a typical uniform con guration all products manufactured by FAAC S p A Bologna 13 December 2007 The Managing Direc...

Page 6: ...s you can use the FAILSAFE function If this function is enabled the unit veri es the operation of the photocells before every closing cycle If you do not intend connecting any device to terminals 2 an...

Page 7: ...EWG und nachfolgende nderung 92 31 EWG und 93 68 EWG Zus tzliche Anmerkung Dieses Produkt wurde den Pr fungen in einer typischen homogenen Kon guration unterzogen alle Produkte stammen aus der Produk...

Page 8: ...i Bet tigung die sofortige Sperre der Automation bewirkt bis ein neuer OPEN Impuls gesendet wird 4 FAIL SAFE Durch die Verwendung dieser Klemme f r den Anschluss des Minuspols der Versorgung der Fotoz...

Page 9: ...odi caci n 93 68 CEE 89 336 CEE y sucesiva modi caci n 92 31 CEE y 93 68 CEE Nota adicional Este producto ha sido sometido a ensayos en una con guraci n t pica homog nea todos productos de fabricaci n...

Page 10: ...n nuevo mando de OPEN 4 FAIL SAFE Utilizando este borne para la conexi n del negativo de la alimentaci n de los transmisores fotoc lulas se puede utilizar la funci n FAILSAFE Si dicha funci n est habi...

Page 11: ...cessive 89 336 CEE et modifications 92 31 CEE et 93 68 CEE successives Note suppl mentaire Ce produit a t soumis des essais dans une con guration typique homog ne tous les produits sont fabriqu s par...

Page 12: ...matisme jusqu une nouvelle commande d OPEN 4 FAIL SAFE En utilisant cette borne pour connecter le n gatif de l alimentation des metteurs des photocellules on peut utiliser la fonction FAILSAFE qui si...

Page 13: ...tlijnen 73 23 EEG en latere wijziging 93 68 EEG 89 336 EEG en latere wijziging 92 31 EEG en 93 68 EEG Aanvullende opmerking Dit product is getest in een gebruikelijke homogene con guratie alle product...

Page 14: ...ndo geeft voor onmiddellijke blokkering van het automatisch systeem tot een nieuw OPEN commando wordt gegeven 4 FAIL SAFE Als deze klem wordt gebruikt om de negatieve voedingsdraad van de zenders van...

Page 15: ...QRWH QRWHV QRWH QRWDV DQPHUNXQJ RSPHUNLQJHQ...

Page 16: ...liegendem Handbuch sind unverbindlich FAAC beh lt sich das Recht vor ohne die wesentlichen Eigenschaften dieses Ger tes zu ver ndern und ohne Verbindlichkeiten in Bezug auf die Neufassung der vorliege...

Reviews: