DTP CrossPoint 84 • Installation
10
For the DTP ports only —
Extron recommends the following practices to achieve full transmission distances up to 330
feet (100 m) and reduce transmission errors.
Use the following Extron XTP DTP 24 SF/UTP cables and connectors for the best
performance:
XTP DTP 24/1000
Non-Plenum 1000’ (305 m) spool
22-236-03
XTP DTP 24P/1000
Plenum 1000’ (305 m) spool 22-235-03
XTP DTP 24 Plug
Package of 10
101-005-02
If not using XTP DTP 24 cable, at a minimum, Extron recommends 24 AWG, solid
conductor, STP cable with a minimum bandwidth of 400 MHz.
Terminate cables with shielded connectors to the TIA/EIA T568B standard only (patch
cables, see
Limit the use of more than two pass-through points, which may include patch points, punch
down connectors, couplers, and power injectors. If these pass-through points are required,
use CAT 6 or 6a shielded couplers and punch down connectors.
ATTENTION:
•
Do not connect these boards to a computer data or telecommunications network.
•
Ne connectez pas ces port à des données informatiques ou à un réseau de télécommunications.
•
Do not use Extron UTP23SF-4 Enhanced Skew-Free AV UTP cable or STP201 cable to link the
matrix switcher to Extron DTP products, XTP matrix switchers, or HDBaseT-enabled devices.
•
N'utilisez pas le câble AV Skew-Free UTP version améliorée UTP23SF-4 ou le câble STP201 pour
relier la grille de commutation aux produits DTP, aux grilles de commutation XTP ou aux appareils
équipés HDBaseT Extron.
•
To ensure FCC Class A and CE compliance, STP cables and STP connectors are required.
•
Afin de s’assurer de la compatibilité entre FCC Classe A et CE, les câbles STP et les connecteurs
STP sont nécessaires.
NOTE:
When using cable in bundles or conduits, consider the following:
•
Do not
exceed 40% fill capacity in conduits.
•
Do not comb the cable for the first 20 meters, where cables are straightened, aligned, and secured
in tight bundles.
•
Loosely place cables and limit the use of tie wraps or hook and loop fasteners.
•
Separate tw
isted pair cables from AC power cables.