Selecting Power Supply Cords
BlackDiamond 12800 Series Switches Hardware Installation Guide
137
Black Diamond SSI DC PSU, Model 60021:
●
Wire: three conductor, 8 AWG, jacketed, and marked 90C min
NOTE
Tray Cable is a UL US-only requirement. Outside United States standard 8 AWG (8.35mm
2
), 90C wire is
acceptable.
●
Wall plug: N/A, 3-conductor wires have been stripped and are ready for connection to DC power
source mains
●
Device connector: Molex Shell Connector PN 42816-0312; Molex Pin Connectors PN 42815-0032
●
Assembly rating: 75VDC, 30A, (Do not disconnect under load)
Black Diamond 325 W AC PSU Model 65021:
●
Wire: 18 AWG (0.82mm2) minimum, 3-conductor flexible cable, Type SVT, SJT, HAR or equivalent,
no longer then 10ft
●
Wall plug: Suitable for use in country of installation & approved by local regulatory authority
●
Device connector: IEC320-C13, 90 degree angle, rated at 15 A, 250 VAC
●
Power cord assembly: Must be rated at 10A by in-country regulatory authority
Black Diamond 325 W DC PSU, Model 60021:
●
Wire: UL LISTED, three conductor, 14 AWG, jacketed, and marked (UL) FT2, 90C min
NOTE
Tray Cable is a UL US-only requirement. Outside United States standard 8 AWG (8.35mm
2
), 90C wire is
acceptable.
●
Wall plug: N/A, 3-conductor wires have been stripped and are ready for connection to DC power
source mains
●
Device connector: Molex Shell Connector PN 42816-0312; Molex Pin Connectors PN 42815-0032
●
Assembly rating: 75VDC, 30A, (Do not disconnect under load)
WARNING!
When using multiple power supplies, make sure that each power supply is attached to independent circuits breakers.
See PS installation instructions of PS for proper sizing of circuit breaker.
Make sure that the source outlet is properly grounded according to the country’s local electrical requirements before
plugging the AC supply power cord into a PSU.
For specific product input power requirements refer to the data sheet of the product or modular PSU at http://
www.extremenetworks.com or to Appendix B of this guide.
The following countries have specific safety instructions concerning power connectors:
●
Argentina: The supply plug must comply with Argentinean standards.
●
Australia: Use AS 3112 for 110/220 VAC power supplies.
●
Denmark: The supply plug must comply with section 107-2-D1, standard DK2-1a or DK2-5a.
●
International: Use CEE 7/7 for 110/220 VAC power supplies.
●
Japan:
Summary of Contents for BlackDiamond 12800 Series
Page 8: ...Table of Contents BlackDiamond 12800 Series Switches Hardware Installation Guide 8...
Page 12: ...Preface BlackDiamond 12800 Series Switches Hardware Installation Guide 12...
Page 13: ...1 BlackDiamond 12800 Series Switches...
Page 14: ......
Page 39: ...2 Installing BlackDiamond Switches and Modules...
Page 40: ......
Page 113: ...3 BlackDiamond Maintenance Procedures...
Page 114: ......
Page 131: ...4 Appendixes...
Page 132: ......
Page 146: ...Safety Information BlackDiamond 12800 Series Switches Hardware Installation Guide 146...
Page 160: ...Index BlackDiamond 12800 Series Switches Hardware Installation Guide 160...