Trips and Fault Finding
7-3
590+ Series DC Digital Converter
Hexadecimal Representation of Trips
The LAST ALARM, HEALTH WORD and HEALTH STORE parameters use a four digit
hexadecimal number to identify individual trips. Each trip has a unique corresponding number as
shown below.
LAST ALARM, HEALTH WORD and HEALTH STORE
LAST ALARM, HEALTH WORD and HEALTH STORE
LAST ALARM, HEALTH WORD and HEALTH STORE
LAST ALARM, HEALTH WORD and HEALTH STORE
Trip
Trip
Trip
Trip
Trip Code
Trip Code
Trip Code
Trip Code
First Digit
First Digit
First Digit
First Digit
Digit
Digit
Digit
Digit
Digit
Digit
Digit
Digit
Last Digit
Last Digit
Last Digit
Last Digit
NO ACTIVE ALARMS
0
OVERSPEED
1
1
MISSING PULSE
2
2
FIELD OVER I
4
3
HEATSINK TRIP *
8
4
THERMISTOR
1
5
OVER VOLTS (VA)
2
6
SPD FEEDBACK
4
7
ENCODER FAILED
8
8
FIELD FAILED
1
9
3 PHASE FAILED *
2
10
PHASE LOCK
4
11
5703 RCV ERROR
8
12
STALL TRIP
1
13
OVER I TRIP
2
14
OTHER
•
4
15
ACCTS FAILED *
8
* Refer to “
Power Board LED Trip
” below
•
For the LAST ALARM parameter, OTHER is replaced with the trip codes below.
LAST ALARM only
LAST ALARM only
LAST ALARM only
LAST ALARM only
14
AUTOTUNE ERROR
F
0
0
1
14
AUTOTUNE ABORTED
F
0
0
2
14
EXTERNAL TRIP
F
0
0
5
14
REMOTE TRIP
F
0
0
6
14
CONFIG ENABLED
F
2
0
0
14
NO OP-STATION
F
4
0
0
14
PCB VERSION
F
F
0
5
14
PRODUCT CODE
F
F
0
6
When more than one trip is to be represented at the
same time then the trip codes are simply added together
to form the value displayed. Within each digit, values
between 10 and 15 are displayed as letters A to F
For example, if the HEALTH WORD parameter is
01A8
then this represents a “1” in digit 3, an “8” and a
“2” in digit 2, (8+2 = 10, displayed as A) and an 8 in
digit 1. This in turn represents the active trips FIELD
FAILED, ENCODER FAILED, OVER VOLTS (VA)
and HEATSINK TRIP (an unlikely situation).
Decimal number
Decimal number
Decimal number
Decimal number
Display
Display
Display
Display
10
A
11
B
12
C
13
D
14
E
15
F
Summary of Contents for 590+ Series
Page 16: ...1 4 Getting Started 590 Series DC Digital Converter ...
Page 76: ...3 50 Installing the Converter 590 Series DC Digital Converter ...
Page 110: ...5 14 The Operator Station 590 Series DC Digital Converter ...
Page 194: ...7 10 Trips and Fault Finding 590 Series DC Digital Converter ...
Page 208: ...9 6 Control Loops 590 Series DC Digital Converter ...
Page 236: ...10 28 Parameter Specification Table 590 Series DC Digital Converter ...
Page 260: ...11 24 Technical Specifications 590 Series DC Digital Converter ...
Page 274: ...12 14 Certification for the Converter 590 Series DC Digital Converter ...
Page 300: ...15 2 The Default Application 590 Series DC Digital Converter ...
Page 308: ......