6-36
Programming Your Application
590+ Series DC Digital Converter
LAST ALARM
Range: See below
The hexadecimal value of the last (or only) alarm. Refer to Chapter 7: “Trips and Fault
Finding” - Alarm Messages.
0x0000 : NO ACTIVE ALARMS
0x0001 : OVER SPEED
0x0002 : MISSING PULSE
0x0004 : FIELD OVER I
0x0008 : HEATSINK TRIP
0x0010 : THERMISTOR
0x0020 : OVER VOLTS (VA)
0x0040 : SPD FEEDBACK
0x0080 : ENCODER FAILED
0x0100 : FIELD FAILED
0x0200 : 3 PHASE FAILED
0x0400 : PHASE LOCK
0x0800 : 5703 RCV ERROR
0x1000 : STALL TRIP
0x2000 : OVER I TRIP
0xf005 : EXTERNAL TRIP
0x8000 : ACCTS FAILED
0xf001 : AUTOTUNE ERROR
0xf002 : AUTOTUNE ABORTED
0xf200 : CONFIG ENABLED
0xf400 : NO OP-STATION
0xf006 : REMOTE TRIP
0xff05 : PCB VERSION
0xff06 : PRODUCT CODE
FIELD FAIL
Range: See below
Inhibits the field fail alarm.
0 : ENABLED
1 : INHIBITED
5703 RCV ERROR
Range: See below
Inhibits 5703 serial communications receive error. Only active in Slave Mode.
0 : ENABLED
1 : INHIBITED
STALL TRIP INHIBIT
Range: See below
(STALL TRIP)
Inhibits the stall trip alarm from tripping the contactor out.
0 : ENABLED
1 : INHIBITED
TRIP RESET
Range: See below
When this is FALSE the faults are latched permanently and the HEALTHY output remains
inactive after toggling the Start input (C3) off/on. The Trip Reset must then be set to TRUE for
the faults to be reset and the HEALTHY output to go active (high) when C3 goes low. This
feature can be used in applications where you want to reset the faults under your own control,
rather than automatically with the Start/Run command.
0 : FALSE
1 : TRUE
SPEED FBK ALARM
Range: See below
Inhibits the speed feedback alarm.
0 : ENABLED
1 : INHIBITED
ENCODER ALARM
Range: See below
Inhibits the encoder option board alarm.
0 : ENABLED
1 : INHIBITED
REM TRIP INHIBIT
Range: See below
Inhibits the remote trip
0 : ENABLED
1 : INHIBITED
REM TRIP DELAY
Range: 0.1 to 600.0 SECS
The delay between the remote trip alarm being activated and the drive tripping.
Summary of Contents for 590+ Series
Page 16: ...1 4 Getting Started 590 Series DC Digital Converter ...
Page 76: ...3 50 Installing the Converter 590 Series DC Digital Converter ...
Page 110: ...5 14 The Operator Station 590 Series DC Digital Converter ...
Page 194: ...7 10 Trips and Fault Finding 590 Series DC Digital Converter ...
Page 208: ...9 6 Control Loops 590 Series DC Digital Converter ...
Page 236: ...10 28 Parameter Specification Table 590 Series DC Digital Converter ...
Page 260: ...11 24 Technical Specifications 590 Series DC Digital Converter ...
Page 274: ...12 14 Certification for the Converter 590 Series DC Digital Converter ...
Page 300: ...15 2 The Default Application 590 Series DC Digital Converter ...
Page 308: ......