ROOM VOLUME for VENT FREE
7
The following formula can be used to determine the maximum heater rating (per the definition of unconfined space) that is
allowed in your space:
Maximum BTU/Hr. =
x 1000
Example A: Consider two connecting rooms with an open area between, with the following dimensions: L1 = 151/2 ft., L2 = 12 ft.,
W = 12 ft., H = 8 ft.
x
1000
=
52,800
BTU/Hr.
Example B: If there were a door between the two rooms the calculation would be based only on the room with the heater.
x 1000 = 29,760 BTU/Hr.
Will my space support a H Series Vent Free Gas Fireplace?
Maximum BTU/hr. my space will support (use formula above)
a) __________________
BTU/hr. of European Home
H Series
Vent Free Gas Fireplace
b) ____37,500________
If the answer to a) is
greater
than b) then your space
will
support the installation of the
H Series
Vent Free Gas Fireplace; if a) is
less
than b) then your space
will not
support an
H Series
Vent Free Gas Fireplace.
(L1 + L2)ft. x (W)ft. x (H)ft.
50
(151/2 + 12)ft. x (12)ft. x (8)ft.
50
(151/2)ft. x (12)ft. x (8)ft.
50
Bringing in Outside (or “Make-up”) Air
Some building code jurisdictions require that outside or “make-up” air be provided when installing a fireplace of this type. This
requirement may be satisfied by the proper installation of an ‘outside air source’ which is not provided. The suitability of any
particular air source ducting system must be made by the installer. Connection to an outside air source is made via the Air Shutter
Kit. See the Air Shutter Kit installation instructions later in this manual.