APPENDIX ONE
Burner
lights when
only pilot
should light
Pilot
holds
flame?
YES
1. Verify transmitter is not powered on or in thermostat mode
calling for heat. Display should say OFF next to thermometer
image on display for thermometer off.
2. Ensure all electrical connections are secure based on the wiring
diagram.
3. Verify proper voltage at the main valve connection ( EV2 green).
- If voltage is present, replace control module.
- If voltage is not present replace gas valve (solenoid not closing).
1. If equipped, check that the continuous pilot switch is ON.
2. Verify pilot flame makes full contact with flame sensor.
- Verify gas pressure on full capacity.
- Verify turbulence is not pushing flame off flame sensor.
3. Clean the flame sensor and inspect wiring for damage.
4. Verify pilot assembly is properly grounded and pilot hood is
brushed clean of debris and securely pressed down.
5. Replace flame sensor.
6. Check voltage at pilot valve connection (EV1 orange).
- If no voltage present when calling for pilot, replace control
module.
- If voltage is present, replace gas valve (valve not opening).
YES
1. Verify electrical connections are properly connected according
to the wiring diagram and replace any damaged harnesses.
2. Verify the pilot flame is properly directed to ignite the burner.
3. Verify piezo is not sparking if so, go back to Piezo Still Sparking.
4. Verify proper components are installed for type of gas used.
5. Check continuity of the main burner coil.
6. Check for voltage at the main burner connection (EV2 green).
- If voltage is present replace gas valve (not opening).
- If no voltage is present replace control module.
NO
NO
Main
burner
ignites?
YES
NO
1. Verify electrical components are properly connected according
to the wiring diagram and replace any damaged harnesses.
2. Verify pilot flame makes contact with flame sensor. Clean flame
sensor of any debris or silicone film.
3. Verify gas pressure on full capacity is according to manual.
4. Check for voltage at the main burner connection (EV2 green).
- If voltage is present when drops out, replace gas valve
- If no voltage, replace control module.
Main
burner
remains
on
YES
NO
[Continued]
TROUBLESHOOTING - Fireplace Doesn’t Work
(cont.)