PRE-INSTALLATION PLANNING
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
HVF-42-P
HVF-60-P
HVF-72-P
Clearance to Top Cabinet Standoffs
0”
Clearance to Cabinet End Standoff
0”
Clearance to Wood Floor
0”
Distance Between Cabinet Bottom and Enclosure Ceiling
341/8”
Distance Between the Opening and a Side Wall in Front of the Fireplace
6.0”
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
When installing the
H Series
Vent Free Gas Fireplace, the clearances shown in the table below must be
observed. If the required clearances are not maintained a fire may result thereby causing property damage,
personal injury or loss of life.
When the fireplace is to be installed directly on carpeting or combustible material other than wood flooring, it
must be installed on a metal or wood panel extending the full width and depth of the fireplace cabinet.
When enclosing your fireplace, the use of non-combustible building materials
is required. Please read and understand the
COMBUSTIBLE MATERIALS and
NON-COMBUSTIBLE MATERIALS
section.
Minimum Clearances to Combustible Materials
Must maintain adequate clearances for servicing and proper operation.