F8 group Fault and protection parameter group
Code
Parameter name
Setting range
Factory setting Change
F8.00
Overcurrent stall gain
0~100
20
☆
F8.01
Lost speed stall protection current
100%~200%
-
☆
F8.02
Overload protection
0:Prohibit; 1:Allow
1
☆
F8.03
Motor overload protection gain
0.20~10.00
1.00
☆
F8.04
Motor overload pre-alarm coefficient
50%~100%
80%
☆
F8.05
Overvoltage stall gain
0(No overvoltage stall)~100
0
☆
F8.06
Overvoltage stall protection voltage /
energy consumption brake voltage
120%~150%(Three-phase)
130%
☆
F8.08
Output phase loss protection
0:Prohibit; 1:Allow
1
☆
F8.09
Short to ground protection
0:Invalid; 1:Valid
1
☆
F8.10
Number of automatic fault reset
0 ~ 32767
0
☆
F8.11
Fault DO action selection during
automatic fault
0:OFF ; 1:ON
0
☆
F8.12
Automatic fault reset
0.1s ~ 100.0s
1.0s
☆
F8.25
Abnormal reserve frequency
60.0% ~ 100.0%
100%
☆
F8.26
Momentary power cut action selection
0: Invalid; 1: Deceleration;
2: Deceleration and stop
0
☆
F8.28
Recovery voltage judgment time of
momentary power cut
0.00s ~ 100.00s
0.50s
☆
F8.29
Judgment voltage of momentary power
cut
50.0% ~ 100.0%(Standard bus voltage)
80%
☆
F9 group Communication parameter group
Code
Parameter name
Setting range
Factory setting Change
F9.00
Baud rate
Unit:Modbus
2: 1200BPS;
3: 2400BPS;
4: 4800BPS;
5: 9600BPS;
6: 19200BPS;
7: 38400BPS;
8: 57600BPS;
9: 115200BPS
Tens digit: Reserved;
Hundreds digit : Reserved
Thousands digit:Reserved
6005
☆
F9.01
Data format
0: No parity (8-N-2);
1: Even parity (8-E-1)
2: Odd parity (8-O-1)
3: No parity (8-N-1)
0
☆
F9.02
This unit address
1 ~ 250 ,for broadcast address
1
☆
F9.03
Response delay
0ms ~ 20ms
2ms
☆
F9.04
Communication timeout time
0.0 (Invalid ); 0.1 ~ 60.0s
0.0
☆
F9.05
Data transfer format selection
Units digit:Modbus
0: Non-standard Modbus protocol;
1: Stand Modbus protocol
Tens digit: Reserved
31
☆
F9.06
Communication read current resolution 0:0.01A ; 1:0.1A
0
☆