F7 group Auxiliary function parameter group
Code
Parameter name
Setting range
Factory setting
Change
F7.00
Jog running frequency
0.00Hz ~ F0.19 (Max. frequency)
6.00Hz
☆
F7.01
Jog acceleration time
0.0s ~ 6500.0s
5.0s
☆
F7.02
Jog deceleration time
0.0s ~ 6500.0s
5.0s
☆
F7.03
Jog priority
0: Invalid; 1: Valid
1
☆
F7.04
Jump frequency 1
0.00Hz ~ F0.19 (Max. frequency)
0.00Hz
☆
F7.05
Jump frequency 2
0.00Hz ~ F0.19 (Max. frequency)
0.00Hz
☆
F7.06
Jump frequency range
0.00Hz ~ F0.19 (Max. frequency)
0.00Hz
☆
F7.07
Jump frequency availability
0: Invalid; 1: Valid
0
☆
F7.08
Acceleration time 2
0.0s ~ 6500.0s
Depends on models
☆
F7.09
Deceleration time 2
0.0s ~ 6500.0s
Depends on models
☆
F7.10
Acceleration time 3
0.0s ~ 6500.0s
Depends on models
☆
F7.11
Deceleration time 3
0.0s ~ 6500.0s
Depends on models
☆
F7.12
Acceleration time 4
0.0s ~ 6500.0s
Depends on models
☆
F7.13
Deceleration time 4
0.0s ~ 6500.0s
Depends on models
☆
F7.14
Switching frequency point between
acceleration time 1 and acceleration time 2
0.00Hz ~ F0.19 (Max. frequency)
0.00Hz
☆
F7.15
Switching frequency point between
deceleration time 1 and deceleration time 2
0.00Hz ~ F0.19 (Max. frequency)
0.00Hz
☆
F7.16
Forward/reverse rotation dead-band
0.00s ~ 3600.0s
0.00s
☆
F7.17
Reverse rotation control
0: Allow; 1: Prohibit
0
☆
F7.18
Mode under lower limit frequency
0: Running at lower limit frequency;
1: Stop; 2: Running at zero speed
0
☆
F7.19
Droop control
0.00Hz ~ 10.00Hz
0.00Hz
☆
F7.20
Setting of power-on arrival time
0h ~ 36000h
0h
☆
F7.21
Setting of running arrival time
0h ~ 36000h
0h
☆
F7.22
Start protection selection
0: OFF; 1: ON
0
☆
F7.23
FDT1 detection value
0.00Hz ~ F0.19 (Max. frequency)
50.00Hz
☆
F7.24
FDT1 detection hysteresis value
0.0% ~ 100.0% (FDT1 level)
5.0%
☆
F7.25
Frequency reaches detection width
0.00 ~ 100% (Max. frequency)
0.0%
☆
F7.26
FDT2 detection value
0.00Hz ~ F0.19 (Max. frequency)
50.00Hz
☆
F7.27
FDT2 detection hysteresis value
0.0% ~ 100.0% (FDT2 level)
5.0%
☆
F7.28
Frequency detection value 1
0.00Hz ~ F0.19 (Max. frequency)
50.00Hz
☆
F7.29
Frequency detection width 1
0.0% ~ 100.0% (Max. frequency)
0.0%
☆
F7.30
Frequency detection value 2
0.00Hz ~ F0.19 (Max. frequency)
50.00Hz
☆
F7.31
Frequency detection width 2
0.0% ~ 100.0% (Max. frequency)
0.0%
☆
F7.32
0 current detection
0.0% ~ 300.0% (Motor rated current)
5.0%
☆
F7.33
0 current delay
0.01s ~ 360.00s
0.10s
☆
F7.34
Current over-run value
0.0% (Not detected);
0.1% ~ 300.0% (Max. frequency)
200.0%
☆
F7.35
Current over-run time
0.00s ~ 360.00s
0.00s
☆
F7.36
Arrival current 1
0.0% ~ 300.0% (Motor rated current)
100.0%
☆
F7.37
Current 1 width
0.0% ~ 300.0% (Motor rated current)
0.0%
☆
F7.38
Arrival current 1
0.0% ~ 300.0% (Motor rated current)
100.0%
☆
F7.39
Current 1 width
0.0% ~ 300.0% (Motor rated current)
0.0%
☆
F7.40
Module temperature arrival
0
℃
~ 100
℃
75
℃
☆
F7.41
Cooling fan control
0: Fan run when inverter is running;
1: Fan keep running
0
☆
F7.42
Timing function selection
0: Invalid; 1: Valid
0
★
F7.43
Timing run time selection
0: F7.44 set; 1: AI1 set;
Note: Analog input range correspond to F7.44
0
★
F7.44
Timing run time
0.0Min ~ 6500.0Min
0.0Min
★
F7.45
Running time arrive
0.0Min ~ 6500.0Min
0.0Min
★
F7.46
Awaken frequency
Dormancy frequency (F7.48)~maximum frequency (F0.19) 0.00Hz
☆
F7.47
Awaken delay time
0.0s ~ 6500.0s
0.0s
☆
F7.48
Dormancy frequency
0.00Hz ~ awaken frequency (F7.46)
0.00Hz
☆
F7.49
Dormancy delay time
0.0s ~ 6500.0s
0.0s
☆
F7.50
AI1 input voltage protection lower limit
0.00V ~ F7.51
3.1V
☆
F7.51
AI1 input voltage protection upper limit
F7.50 ~ 10.00V
6.8V
☆