F4 group V/F control parameter group
Code
Parameter name
Setting range
Factory setting Change
F4.00
V/F curve setting
0: Linear V/F;
1: Multi-point V/F;
2: Square V/F;
3: 1.2th power V/F;
4: 1.4th power V/F;
6: 1.6th power V/F;
8: 1.8th power V/F;
10: V/F completely separate;
11: V/F half separate
0
★
F4.01
Torque boost
0.0% (Automatic torque boost)
0.1~30%
0.0%
★
F4.02
Torque boost cut-off frequency
0.00Hz~F0.19 (Max. Frequency)
15.00Hz
★
F4.03
Multi-point V/F frequency point 1
0.00Hz~F4.05
0.00Hz
★
F4.04
Multi-point V/F voltage point V1
0.0%~100.0%
0.0%
★
F4.05
Multi-point V/F frequency point 2
F4.03~F4.07
0.00Hz
★
F4.06
Multi-point V/F voltage point V2
0.0%~100.0%
0.0%
★
F4.07
Multi-point V/F frequency point 3
F4.05~b0.04 (Motor rated frequency)
0.00Hz
★
F4.08
Multi-point V/F voltage point V3
0.0%~100.0%
0.0%
★
F4.09
V/F slip compensation gain
0.0%~200.0%
0.0%
☆
F4.10
V/F overexcitation gain
0~200
80
☆
F4.11
V/F oscillation suppression gain
0~100
0
☆
F4.12
V/F separation voltage source
0~9
0
☆
F4.13
V/F separation voltage digital setting
0V~motor rated voltage
0V
☆
F4.14
V/F separation voltage rise time
0.0s~1000.0s
0.0s
☆
F5 group Vector control parameter group
Code
Parameter name
Setting range
Factory setting Change
F5.00
Proportion of speed loop G1
1 ~ 100
30
☆
F5.01
Speed loop integral T1
0.01s ~ 10.00s
0.50s
☆
F5.02
Switching frequency 1
0.00 ~ F5.05
5.00Hz
☆
F5.03
Proportion of speed loop G2
0 ~ 100
20
☆
F5.04
Speed loop integral T2
0.01s ~ 10.00s
1.00s
☆
F5.05
Switching frequency 2
F5.02 ~ F0.19(Max. frequency)
10.00Hz
☆
F5.06
Speed loop integral
0: Invalid; 1: Valid
0
☆
F5.07
Torque limit source under speed control
mode
0: Function code F5.08 set; 1: AI1 set;
5: Communication set
0
☆
F5.08
Torque upper limit digital setting
0.0% ~ 200.0%
150.0%
☆
F5.09
Vector control differential gain
50% ~ 200%
150%
☆
F5.10
Speed loop filtering time
0.000s ~ 0.100s
0.000s
☆
F5.11
Vector control overexcitation gain
0 ~ 200
64
☆
F5.12
Excitation regulator proportional gain
0 ~ 60000
2000
☆
F5.13
Excitation regulator integral gain
0 ~ 60000
1300
☆
F5.14
Torque regulator proportional gain
0 ~ 60000
2000
☆
F5.15
Torque regulator integral gain
0 ~ 60000
1300
☆