12
13
EURN010000_
002_C
EURN010000_
002_C
F2 group Output terminal
Code
Parameter name
Setting range
Factory setting Change
F2.02
Relay output function selection (TA.TC) 0~40
2
☆
Relay output function description:
Setting
value
Functions
Description
0
No output
No output action
1
Inverter running
Inverter is in running state, the output frequency (Can be zero),the output ON signal.
2
Fault output (Fault down )
When the drive fails and downtime, the output ON signal.
3
Frequency level detection FDT1 output Please refer to the function code F7.23, F7.24’s instructions.
4
Frequency arrival
Please refer to the description of function code F7.25.
5
Zero-speed running (No output when
shutdown)
Inverter operation and the output frequency is 0, output ON signal. When the drive is shut
down, the signal is OFF.
6
Motor overload pre-alarm
Before the motor overload protection, according to the overload pre-alarm threshold value
judgment, more than the pre-alarm threshold value output ON signal. Motor overload
parameter settings refer to the function code F8.02~F8.04.
7
Inverter overload pre- alarm
Before the inverter overload occurs 10s, output ON signal. Setup counter arrive.
8
Setup counter arrive
When the count reaches the set value of E0.08, output ON signal. Specifies the count value
reaches.
9
Specifies the count value reaches
When the count reaches the set value of E0.09, output ON signal. Counting Function
Reference E0 group.
10
Length arrival
When the actual length of the detection of more than E0.05 set length, output ON signal.
11
PLC cycle is complete
After simple PLC completes one cycle, the output of a pulse width of 250ms signal.
12
Total running time arrival
Inverter total running time of more than F7.21 F6.07 set time,the output ON signal.
13
Limited in frequency
When the set frequency exceeds the upper limit frequency or lower frequency, and output
frequency is beyond the upper limit frequency or lower limit frequency, output ON signal.
14
Torque limiting
Drive under the speed control mode, when the output torque reaches the torque limit, the
inverter is stall protection status, while the output ON signal.
15
Ready to run
When the inverter main circuit and control circuit power supply has stabilized, and the drive
does not detect any fault information, the drive is in an operational state, output ON signal.
17
Upper frequency arrival
When the operating frequency reaches the upper frequency,output ON signal.
18
The lower frequency arrival
(No output when shutdown)
When the operating frequency reaches the lower frequency, output ON signal. The next stop
status signal is OFF.
19
Under voltage state output
When the inverter is in an undervoltage condition, output ON signal.
20
Communication setting
Refer to the communication protocol.
23
Zero-speed operation 2
(Shutdown also output)
The inverter
‟
s output frequency is 0, output ON signal. The signal is also ON when shutdown.
24
Cumulative power-on time arrival
When the inverter’s accumulated power on time (F6.08) over F7.20 the set time, the output ON
signal.
25
Frequency level detection FDT2 output Please refer to the function code F7.26, F7.27’s instructions.
26
Frequency 1 reaches output
Please refer to the function code F7.28, F7.29’s instructions.
27
Frequency 2 reaches output
Please refer to the function code F7.30, F7.31’s instructions.
28
Current 1 reaches output
Please refer to the function code F7.36, F7.37’s instructions.
29
Current 2 reaches output
Please refer to the function code F7.38, F7.39’s instructions.
30
Timing reach output
When the timer function selection (F7.42) is valid, the drive time to reach this run after the set
time runs out, output ON signal.
31
AI1 input overrun
When the value of analog input AI1 greater than F7.51 (AI1 input protection limit) or less than
F7.50 (AI1 input protection under), output ON signal.
33
Off load
When the inverter is off-load state, output ON signal.
34
Reverse operation
Inverter in reverse run, output ON signal
35
0 current state
Refer to the description of function code F7.32, F7.33.
36
Module temperature reaches
Inverter module heatsink temperature (F6.06) reach the set module temperature reaches value
(F7.40), output signal ON.
37
Software current limit
Please refer to the function code F7.34, F7.35’s instructions.
38
The lower frequency arrival
(Stop and output)
When the operating frequency reaches the lower limit frequency, output ON signal. In
shutdown state of the signal is also ON.
40
Current running time of arrival
When the inverter starts running time is longer than the time set by F7.45, it outputs ON signal.