CU-DIN R 4-CH 16 A KNX
CU-DIN R 8-CH 16 A KNX
32 / 54
CU-DIN R 12-CH 16 A KNX
USER MANUAL
Threshold 2 value is 0–255
Set threshold 2 value between 0 and 255. Default is 180.
Options:
0–255
“Threshold input (0–255)” after bus voltage recovery
After a bus voltage recovery, the threshold value is set to the set value.
Options:
0–255
{Input object value<lower threshold}
If the value of the receiving telegram from the bus is lower than the minimum
threshold value, the switch will be activated according to the below options (ON
or OFF or no action)
Options:
Unchange
ON
OFF
Unchange: The channel switch position does not change.
ON:
The channel switch position is set to ON.
OFF: The channel switch position is set to OFF.
{Lower threshold<=Object value<=Upper threshold}
If the value of the receiving telegram from the bus is between the lower
threshold and upper threshold, the switch will be activated according to the
below options (ON or OFF or no action)
Options:
Unchange
ON
OFF
Unchange: The channel switch position is not changed.
ON: The channel switch position is set to ON.
OFF: The channel switch position is set to OFF
{Input object value>upper threshold}
If the value of the receiving telegram from the bus is more than the upper
threshold value, the switch will be activated according to the below options (ON
or OFF or no action)
Options:
Unchange
ON
OFF
Unchange: The channel switch position is not changed.
ON: The channel switch position is set to ON.
OFF: The channel switch position is set to OFF