CU-DIN R 4-CH 16 A KNX
CU-DIN R 8-CH 16 A KNX
34 / 54
CU-DIN R 12-CH 16 A KNX
USER MANUAL
Threshold 2 value is (0–65,535)
Set threshold 2 value between 0 and 65,535. Default is 180.
Options:
0– 65,535
“Threshold input (0– 65,535)” after bus voltage recovery
The default input threshold value is set after power on recovery
Options:
0– 65,535
{Input object value<lower threshold}
If the value of the receiving telegram from the bus is lower than the minimum
threshold value, the switch will be activated according to the below options (ON
or OFF or no action)
Options:
Unchange
ON
OFF
Unchange: The channel switch position does not change
ON:
The channel switch position is set to ON.
OFF: The channel switch position is set to OFF.
{Lower threshold<=Object value<=Upper threshold}
If the value of the receiving telegram from the bus is between the lower
threshold and upper threshold, the switch will be activated according to the
below options (ON or OFF or no action)
Options:
Unchange
ON
OFF
Unchange: The channel switch position is not changed.
ON: The channel switch position is set to ON.
OFF: The channel switch position is set to OFF
{Input object value>upper threshold}
If the value of the receiving telegram from the bus is more than the upper
threshold value, the switch will be activated according to the below options (ON
or OFF or no action)
Options:
Unchange
ON
OFF
Unchange: The channel switch position is not changed.
ON: The channel switch position is set to ON.
OFF: The channel switch position is set to OFF