CU-DIN R 4-CH 16 A KNX
CU-DIN R 8-CH 16 A KNX
19 / 54
CU-DIN R 12-CH 16 A KNX
USER MANUAL
Alarm when counter out (10–10,000,000)
This parameter sets the value for the counter (out) alarm.
Options:
10–10,000,000
Alarm telegram interval when counter out (1–255 s)
This parameter sets the ON-counter overflow interval between alarm telegrams.
Options:
1–255 s
Alarm telegram number (1–255, 0 – unlimited)
This parameter sets the ON counter overflow alarm number.
Options:
0–unlimited
1–255
The switch state on bus voltage failure
When the bus voltage fails, this function will give a reaction. Three choices will
be available as follows:
Options:
Unchange
ON
OFF
Unchange: The channels switch position will be unchanged after bus voltage
failure.
ON:
The channel will switch ON after bus voltage failure
OFF: The channel will switch OFF after bus voltage failure
The Operation of switch after bus voltage recovery
When power is on during bus voltage recovery, this function will be executed.
Four choices will be available as follows:
Options:
Unchange
Recovery
ON
OFF
Unchange: The channel switch position will be unchanged after bus voltage
recovery.
Recovery: After bus voltage recovery, the channel switch position will revert to its
state at the previous power-down.
ON: The channel position will switch ON after bus voltage recovery.
OFF: The channel position will switch OFF after bus voltage recovery.
Show the function page
If this parameter is activated, the channel function page will be shown. The
function page offers Time, Scene, Threshold, Blinds and Logic. For details see
the following sections.