CU-DIN R 4-CH 16 A KNX
CU-DIN R 8-CH 16 A KNX
29 / 54
CU-DIN R 12-CH 16 A KNX
USER MANUAL
Fig 9: Scene function window
10 scenes can be configured for each channel. Each scene can be set to ON or
OFF.
The scene will be activated by receiving a telegram value from the bus. The
value of the telegram (bit 0–6) is equal to a scene number. The seventh bit of
the telegram must be 0 to start the scene.
The scene is stored by receiving a telegram value from the bus. The value of the
telegram (bit 0–6) is equal to a scene number. The scene state is the current
switch state. The bit seven value of the telegram must be 1 to store the scene.
Output is assigned to scene 1–64 or not allocated
Options:
Not allocated
Scene No. 01
Scene No. 02
………………
Scene No. 64
The scene number is between 1 and 64, the value is between 0 and 63 or not
allocated.