CU-DIN R 4-CH 16 A KNX
CU-DIN R 8-CH 16 A KNX
52 / 54
CU-DIN R 12-CH 16 A KNX
USER MANUAL
6.2.13 Objects “Logic”
NO Object name
Function
Flags
Data type
26 Output A
Logic
connection 1
C W U
EIS1
DPT 1.002
1 bit
If this function has been activated, this communication object will show and
the logic function is valid. The logic functions include: AND, OR, XOR and
GATE.
27 Output A
Logic
connection 2
C W U
EIS1
DPT 1.002
1 bit
If this function has been activated, this communication object will show and
the logic function is valid. The logic functions include: AND, OR, XOR and
GATE.
Table 16. Logic
6.2.14 Objects “Heating”
NO Object name
Function
Flags
Data type
10 Output A
Heat with 1 bit
control
C W U
EIS1
DPT 1.001
1 bit
If the heating actuator is selected this communication object is available.
Start PWM by receiving telegram “1”, stop PWM by receiving telegram “0” ,
start running automatically when power on, and set by ETS.
10 Output A
Heat with 1 byte
control
C W U
EIS14
DPT 5.004
1 byte
If “heat with byte control” is selected, this communication object is valid. Can
change value of PWM by receiving 1 byte data. Output ON if receiving value is
255, output OFF if receiving value is 0, otherwise output PWM according to
the receiving value of telegram from bus.
Table 17. Heating actuator