- Secondary control output low limit - [r.E08]
This parameter is available when one control output is
configured as secondary control output.
Range: From 0.0 % of the output span to S.OLH [r.E09].
- Secondary control output high limit - [r.E09]
This parameter is available when one control output is
configured as secondary control output.
Range: from S.OLL [r.E08] to 100.0 % of the output span
- Secondary control output max rate of rise
- [r.E10]
This parameter is available when one control output is
configured as secondary control output.
Ranges: from 0.1%/s to 25.0%/s.
Above this value the display shows “Inf” meaning that no limit is
imposed
NOTES
:
1) This parameter will be active even if device is configured for
On/OFF control.
2) During the transfer from AUTO to MANUAL, if this action is
programmed as a not bumpless transfer, the “S.rñP” function
will be ignored and the output will step up to the value set by
“Añ.UL” [C.G04] parameter.
- Secondary output cycle time - [r.E11]
This parameter is available when a time proportional secondary
control output is configured.
Range: from 1 to 200 s
- Set point low limit - [r.E12]
Range: From “ñ.In.L” [C.d05] to rH [r.E13].
NOTES
: Whenever “ñ.In.L” [C.d05] has been modified, the
following occurs:
1) rL will be realigned to it;
2) if the set point values are out of the new limits, the set point
automatically assumes the default value.
Xkc-1-C0.P65
5/29/02, 11:59 AM
86
Summary of Contents for MKC
Page 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...
Page 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...
Page 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...
Page 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...
Page 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...
Page 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...