CnF. 1
37
Cnd.A= The auxiliary input activation is controlled by its
status (The device works with local set point
when auxiliary input is out of range, while it
works with remote set point (or bias) when it is
within range)
NOTE
: The parameter “L.r.O.ñ” (local/remote set point operative
mode [C.d16]) will be forced to “n.ALG” if “A.In.F” (auxiliary input
function [C.d09]) is equal to “bIAS” and “A.I.Añ” (auxiliary input
activation mode [C.d14]) is equal to “Cnd.A”.
- Auxiliary input safety condition - [C.d15]
This parameter is available only when auxiliary input is
configured and "A.i.Añ" [C.d14] is equal to "norñ".
Range: nonE = when the auxiliary input is out of range, the
instrument operates as in presence of the min
or max auxiliary input value.
Cnd.A = when the auxiliary input is out of range, the
control output goes to safety value “SF.UL”
(output safety value [C.G08]).
If servomotor open loop control drive is
configured the “Safety value” "SF.UL" [C.G08]
has no effect and the instrument operates in
accordance with “SF.Cn” (Output safety
condition [C.G07]) parameter setting.
NOTE:
The “SF.Cn” (Output safety condition” [C.G07]) has the
priority on “A.I.Sc” (auxiliary input safety condition [C.d15]).
- Local/remote set point operative mode
- [C.d16]
This parameter is available only when auxiliary input is
configured
Range: ALG = when the transfer from remote to local set point
is performed, the local set point value will be
aligned to last remote set point value.
n.ALG = when the transfer from remote to local set point
is performed, the local set point value will not
be changed (The programmed ramps Grd1
[r.E14] and Grd2 [r.E15] may be activated).
NOTES
:
1) The selected local set point will be changed even if it is
software protected.
2) The parameter is forced to “n.ALG” if “A.In.F” (auxiliary input
function [C.d09]) is equal to “bIAS” and “A.I.Añ” (auxiliary
input activation mode [C.d14]) is equal to “Cnd.A”
Xkc-1-C0.P65
5/29/02, 11:59 AM
37
Summary of Contents for MKC
Page 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...
Page 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...
Page 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...
Page 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...
Page 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...
Page 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...