CnF. 5
56
- Event 1 function - [C.H07]
This parameter will be available only when OUT 1 is configured
as event annunciator ("O1.Fn" [C.E01] is equal to “Eun.1”).
Range: ñ.In.E= Error condition (Over-Under-Open-Shrt) on
main input (Logic level “1” when error occurs)
Cj.Er = Error condition on CJ measurement (Logic level
“1” when error occurs)
A.In.E= Error condition (Over-Under-Open) on auxiliary
input (Logic level “1” when error occurs)
ñEA.E = Error condition on any measurement (Logic
level “1” when error occurs)
Au.ñA = Auto/manual mode annunciator (Logic level “1”
when device is in manual mode)
SP.L.r = Local/Remote set point annunciator (Logic level
“1” when remote set point is used)
- Event 1 contact status - [C.H08]
This parameter will be available only when OUT 1 is configured
as event annunciator ("O1.Fn" [C.E01] is equal to “Eun.1”).
Range: CLSd = The output is at logic level “1” when contact is
closed
OPEn = The output is at logic level “1” when contact is
open
- Event 2 function - [C.H09]
This parameter will be available only when OUT 2 is configured
as event annunciator ("O2.Fn" [C.E02] is equal to “Eun.2”).
Range: ñ.In.E= Error condition (Over-Under-Open-Shrt) on
main input (Logic level “1” when error occurs)
Cj.Er = Error condition on CJ measurement (Logic level
“1” when error occurs)
A.In.E= Error condition (Over-Under-Open) on auxiliary
input (Logic level “1” when error occurs)
ñEA.E = Error condition on any measurement (Logic
level “1” when error occurs)
Xkc-1-C0.P65
5/29/02, 11:59 AM
56
Summary of Contents for MKC
Page 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...
Page 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...
Page 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...
Page 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...
Page 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...
Page 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...