CnF. 6
61
- Set point display type - [C.I07]
Range: Fn.SP = When device is in normal display mode and it is
performing a set point ramp, the middle display
will show the final set point value.
OP.SP= When device is in normal display mode and it is
performing a set point ramp, the middle display
will show the operative set point value.
NOTE
: This selection has effect only when local set points are
used
- Servomotor behaviour when the output
power is limited - [C.I08]
This parameter will be available only when the close loop
servomotor control drive is configured
Range: bAL
= When the PID output reaches the specific
output limits ("Main control output low limit"
[r.E04] or "Main control output high limit" [r.E05]
or "Secondary control output low limit" [r.E08] or
"Secondary control output high limit" [r.E09])
the instrument will reach the respective limit
and than it will maintain the output relay in open
condition.
n.bAL = When PID value is higher than "Main control
output high limit" [r.E05] or "Secondary control
output high limit" [r.E09] the OUT 3 (
s
) relay
contact is ever closed.
When PID value is lower than "Main control
output low limit" [r.E04] or "Secondary control
output low limit" [r.E08] the OUT 4 (
t
) relay
contact is ever closed.
- Input threshold to enable the soft start
- [C.I09]
Range: for TC/RTD ranges - within the input range;
for linear input - within “ñ.In.L” ("Read-out initial scale
value" [C.d05]) and ”ñ.In.H” ("Read-out full
scale value" [C.d06]).
NOTE
: At start up if the measured value is lower than threshold
value, the device maintains the output power limiting (”ñ.OLL”
[r.E04], ”ñ.OLH” [r.E05], ”S.OLL” [r.E08] and ”S.OLH” [r.E09]) for
a programmed time (“tOL” [rE.16]).
This function is called “soft start”
This threshold value has no effect if “tOL” [rE.16] = InF or when
one logic input is configured for output limiter activation
Xkc-1-C0.P65
5/29/02, 11:59 AM
61
Summary of Contents for MKC
Page 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...
Page 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...
Page 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...
Page 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...
Page 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...
Page 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...