CnF. 3
49
- Secondary control output initial scale value
- [C.F15]
This parameter will be available only when "S.SCL" ("Secondary
control output in engineering units" [C.F13]) is set to "YES".
Range: from -199 to 999
- Secondary control output full scale value
- [C.F16]
This parameter will be available only when "S.SCL" ("Secondary
control output in engineering units" [C.F13]) is set to "YES".
Range: From -199 to 999
- Secondary output auxiliary conditioning
- [C.F17]
This parameter will be available only when secondary control
output is configured and “SC.Cn” ("Secondary control output
conditioning" [C.F12]) is different from “norñ”.
Range: bEFr = The functions listed at Note (**) are calculated
before
to apply the action selected by “SC.Cn”
("Secondary control output conditioning"
[C.F12]) parameter.
AFtr
= The functions listed at Note (**) are calculated
after
to apply the action selected by “SC.Cn”
(“Secondary control output conditioning”
[C.F12]) parameter.
General note on configuration group 3
Exiting from the configuration group 3 the instrument automati-
cally tests the "SPLt" parameter (Split range [C.F01]). When
"SPLt." parameter is enabled (= "Enb"), the instrument performs
the following actions:
1)
If “Añ.UL” parameter ("Output value for AUTO to MAN
transfer [C.G04]) is lower than 0, it will be forced to “buñ“.
2)
If the “SF.UL” parameter ("Output safety value" [C.G08]) is
lower than zero, it will be forced to zero.
3)
If the “IP” parameter ("Integral pre-load" [r.d05] is lower than
zero, it will be forced to 50.0.
Xkc-1-C0.P65
5/29/02, 11:59 AM
49
Summary of Contents for MKC
Page 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...
Page 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...
Page 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...
Page 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...
Page 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...
Page 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...