In presence of an main input out-of-range condition, the control
outputs operate as follows:
a) When “SF.Cn” [C.G07] is set to “Std.”:
a.1) An OVERRANGE is detected and
- the device is set for one control output only, the output
will be forced to 0 % (if reverse action is programmed)
or to 100% (if direct action is programmed).
- the device has two control outputs, the “Main” output is
forced to 0 % and “Secondary” output is forced to 100%.
a.2) An UNDERRANGE is detected and
- the device is set for one output only, the output is
forced to 100 % (if reverse action is programmed) or to
0 % (if direct action is programmed).
- the device has two control outputs, the “Main” output is
forced to 100 % and “Secondary” output is forced to 0
%
b) With “SF.Cn” [C.G07] set to “Ov.Un”, when an overrange or
an underrange condition is detected, the power output is
forced to the safety value “SF.UL” [C.G08].
c) When “SF.Cn” [C.G07] is set to “OvEr”
c.1) if an overrange condition is detected, the power output is
forced to the safety value “SF.UL” [C.G08]
c.2) if an underrange condition is detected the instrument will
operate as described at point a.2).
d) When “SF.Cn” [C.G07] is set to “Undr”
d.1) if an underrange condition is detected, the power output
is forced to the safety value “SF.UL” [C.G08]
d.2) if an overrange condition is detected the instrument will
operate as described at point a.1).
NOTE
: IN ALL CASES ABOVE DESCRIBED THE OUTPUTS
WILL BE FURTHER INFLUENCED BY “OUTPUT CONDITION-
ING”
Xkc-1-C0.P65
5/29/02, 11:59 AM
103
Summary of Contents for MKC
Page 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...
Page 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...
Page 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...
Page 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...
Page 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...
Page 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...