ero electronic MKC User Manual Download Page 117

113

Anti reset windup

: from 10 % to 200 % of the input span.

Main output cycle time

: from 1 second to 200 seconds.

Secondary output cycle time

: from 1 second to 200 seconds.

Relative secondary output gain

: keyboard programmable from

0.20 to 2.00 referred to the proportional band.

Overlap / dead band 

: keyboard programmable from - 20 %

(dead band) to + 50 % (overlap) of the proportional band.

Output limiters

.

For the main and/or secondary control outputs it is possible to
set:
- output high limits
- output low limits
- output max. rate of rise.

AUTO/MANUAL mode

: selectable by front push-button or logic

input.

OUTPUTS

Control output updating time 

:

- 125 ms when a linear input is selected
- 250 ms when a TC or RTD input is selected.

Action

: direct/reverse programmable

Output level limiter

:

- high and low limits for main control output
- high and low limits for secondary control output.

Out 1 and 2
Function

: singularly programmable as

- Control output
- Alarm output
- Event output.

Type

: Relay, SSR or TRIAC.

Out 1 and 2 - Relay
Relay type

: SPDT

Contact rating

: 3 A @ 250 V on resistive load.

Xkc-1-C0.P65

5/29/02, 11:59 AM

113

Summary of Contents for MKC

Page 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...

Page 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...

Page 3: ...27 RUN TIME MODE 62 Display function 62 Indicators 64 Bargraph description 65 OUT failure detection function OFD 66 Direct access to the set point 66 Manual function 67 Serial link 68 Lamp test 69 SMA...

Page 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...

Page 5: ...is shipped with rubber panel gasket 50 to 60 Sh To assure the IP65 and NEMA 4 protection insert the panel gasket between the instrument and the panel as shown in fig 1 While holding the instrument ag...

Page 6: ...2 OUTLINE AND CUT OUT DIMENSIONS Fig 2 A OUTLINE AND CUT OUT DIMENSIONS FOR PKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 2...

Page 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...

Page 8: ...4 CONNECTION DIAGRAMS Fig 3 A PKC REAR TERMINAL BLOCK Fig 3 B MKC REAR TERMINAL BLOCK Xkc 1 C0 P65 5 29 02 11 59 AM 4...

Page 9: ...cause errors in measurement due to excessive and or not balanced line resistance or possible leakage currents A 1 TC INPUT Fig 4 THERMOCOUPLE INPUT WIRING NOTES 1 Don t run input wires together with...

Page 10: ...or V 3 1 _ G mA mV or V 1 3 4 RTD 1 3 4 RTD 1 3 A 2 RTD INPUT Fig 5 RTD INPUT WIRING NOTES 1 Don t run input wires together with power cables 2 Pay attention to the line resistance a high line resist...

Page 11: ...rrents 4 The input impedance is equal to 5 W for 20 mA input 1 MW for 60 mV input 200 kW for 5 V input 400 kW for 10 V input A 4 2 3 AND 4 WIRE TRANSMITTER INPUT Fig 7 A INPUTS WIRING FOR 2 WIRE TRANS...

Page 12: ...tance a high line resistance may cause measurement errors Shield _ mA or V 6 5 _ G mA or V 5 6 Fig 7 C INPUTS WIRING FOR 4 WIRE TRANSMITTER NOTES 1 Don t run input wires together with power cables 2 P...

Page 13: ...ly to avoid ground loop currents 5 The input impedance is equal to 5 W for 20 mA input 200 kW for 5 V input 400 kW for 10 V input C LOGIC INPUT Fig 9 A LOGIC INPUTS DIG 1 2 and 3 WIRING Fig 9 B LOGIC...

Page 14: ...failure detection function see page 66 Fig 9 c LOGIC INPUTS IN 5 6 7 and 8 WIRING NOTES 1 Do not run logic input wiring together with power cables 2 Use an external dry contact capable of switching 0...

Page 15: ...Do not run current transformer input wiring together with AC power cables 3 The minimum active period to perform this measurement is equal to 120 ms 4 The input impedance is equal to 20 W E 1 RELAY O...

Page 16: ...from OUT 1 to OUT 4 are equipped with relays having contact rating equal to 3A 250V AC on resistive load WARNING When OUT 3 and 4 are used as independent relay outputs the addition of the two currents...

Page 17: ...l relay contacts are protected by varistor against inductive load with inductive component up to 0 5 A The following recommendations avoid serious problems which may occur when using relay output for...

Page 18: ...te relay E 3 TRIAC OUTPUTS Fig 14 TRIAC OUTPUT WIRING 23 Load 24 Line 26 Load 27 Line OUT 1 OUT 2 E 2 VOLTAGE OUTPUTS FOR SSR DRIVE Fig 13 SSR DRIVE OUTPUT WIRING Logic level 0 Vout 0 5 V DC Logic lev...

Page 19: ...ower line at the end of the wiring procedure 2 For power connections use No 16 AWG or larger wires rated for at last 75 C 3 Use copper conductors only 4 Don t run input wires together with power cable...

Page 20: ...e at the end of the wiring procedure 3 For servomotor connections use No 16 AWG or larger wires rated for at last 75 C 4 Use copper conductors only 5 Don t run input wires together with power cables 6...

Page 21: ...g across the interconnection cable as defined by EIA for RS 485 a The A terminal of the generator shall be negative with respect to the B terminal for a binary 1 MARK or OFF state 21 20 COMMON 22 B B...

Page 22: ...e A terminal of the generator shall be positive with respect to the B terminal for a binary 0 SPACE or ON 4 The EIA standard establishes that by RS 485 interface it is possible to connect up to 30 dev...

Page 23: ...breaker shall be included in the building installation it shall be in close proximity to the equipment and within easy reach of the operator it shall be marked as the disconnecting device for the equ...

Page 24: ...103 see fig 20 according to the desired input type as shown in the following table J103 INPUT TYPE T C RTD 60 mV 5 V 10 V 20 mA 1 2 open open close open open 3 4 open open close close open 5 6 open op...

Page 25: ...ype as shown in the following table J102 INPUT TYPE 5 V 10 V 20 mA 1 2 close open open 3 4 close close open 5 6 open open close 7 8 open open close 5 7 open close open 6 8 open open open 1 3 5 7 2 4 6...

Page 26: ...ay the current running in a load driven by a time proportional control output during the ON and OFF periods of the output cycle time By this feature it is also available the Out failure detection func...

Page 27: ...th many options Two integrated circuits KY101 and KY103 located as shown in fig 22 and inserted in a socket give you the possibility to verify if your instrument is equipped with the desired option Wh...

Page 28: ...nations are reserved SECURITY CODE SETTING MODE General notes The instrument parameters are divided in two families and each family is divided in groups The first family encompasses all the run time p...

Page 29: ...he display will show On when S run is different from 0 or 1 0 when S run is equal to 0 1 when S run is equal to 1 When the security code is forgotten a new value can be set 2 When S run is different f...

Page 30: ...groups of the run time mode Configuration security code The display will show Note the middle display shows the actual status of the configuration security code 0 1 or On By s and t push button set S...

Page 31: ...used to select a parameter group FUNC o when the instrument is in normal display mode it changes the indication on the lower display see display function o During parameter modification it allows you...

Page 32: ...n they allow you to increase decrease the value under modification with higher rate s MAN or t MAN During parameter modification they allow you to jump to the max or min programmable value NOTES 1 All...

Page 33: ...eter setting the instrument returns automatically to the normal display mode By s or t push button it is possible to select between monitor this selection allows you to monitor but not to modify the v...

Page 34: ...ate as in run time mode 2 During monitor mode if no push button is depressed for more than 10 s or 30 s according to t out C I10 parameter setting the instrument returns automatically to the normal di...

Page 35: ...vo all the parameters related with servomotor output will be skipped 2 During configuration parameters modify mode the upper display shows the selected parameter group the lower display shows the mnem...

Page 36: ...to 1820 C 11 TC G or W From 0 to 2300 C 12 TC D or W3 From 0 to 2300 C 13 TC C or W5 From 0 to 2300 C 14 TC Ni Ni18 Mo From 0 to 1200 C 15 RTD Pt100 From 200 to 850 C 16 TC L From 150 to 1650 F 17 TC...

Page 37: ...33 Linear From 0 to 5 V 34 Linear From 1 to 5 V 35 Linear From 0 to 10 V 36 Linear From 2 to 10 V 37 Linear From 0 to 60 mV 38 Linear From 12 to 60 mV For these ranges it is possible to select a read...

Page 38: ...rom initial range value to In H read out full scale value C d06 for TC RTD input NOTE Changing the value of this parameter the brG L bargraph initial scale value C I03 and rL set point low limit r E12...

Page 39: ...used rSP Input used as remote set point input bIAS Input used as bias for local set point NOTES 1 When auxiliary input option is not mounted the middle display will show no Pr not present 2 The param...

Page 40: ...ead out of the auxiliary input C d12 This parameter is available only when auxiliary input is configured Range from 1999 to 9999 NOTE the decimal point will be automatically positioned as selected for...

Page 41: ...8 If servomotor open loop control drive is configured the Safety value SF UL C G08 has no effect and the instrument operates in accordance with SF Cn Output safety condition C G07 parameter setting NO...

Page 42: ...rammed span for the linear input If it is wrong the device will show CONFIGURATION GROUP 2 C Exx OUTPUTS CONFIGURATION OUT 1 function C E01 Range nonE Output not used Ain Time proportional main contro...

Page 43: ...as secondary control output OUT 4 function C E04 Range nonE Output not used Ain Time proportional main control output SECn Time proportional secondary control output ALr 4 Alarm 4 output Eun 4 Event...

Page 44: ...option circuitry is not mounted the middle display will show no Pr not present OUT 5 range C E08 This parameter will be available only when Out 5 is configured O5 Fn C E07 different from nonE Range 0...

Page 45: ...output linear PV rt Process variable retransmission SP rt Operative set point retransmission NOTE When the option circuitry is not mounted the middle display will show no Pr not present OUT 6 range C...

Page 46: ...he instrument verifies automatically the congruence of all parameters If a wrong setting is detected the device will show The group 2 parameter passes the congruence test when 1 Only one of the 6 outp...

Page 47: ...ter Fd Ou Out failure detection output assignment C I13 will be forced to nonE if it is assigned to an output configured as control output F The parameter IP Integral pre load r d05 will be forced to...

Page 48: ...econd one operates from 33 3 to the 100 of the calculated output Where A 0 B C 33 3 D 100 We will set Bias 1 0 Gain 1 100 33 3 0 3 Bias 2 33 3 Gain 2 100 100 33 3 1 5 A B C D 0 100 100 Calculated PWR...

Page 49: ...cases it is advisable to linearize the ratio between flow rate and valve travel in order to obtain a better control of the process The bias and gain of the two split outputs are the following C bS C F...

Page 50: ...only when main control output is configured Range nO Scalable is not required YES Scalable is required NOTE This scaling allows you to display the output value in engineering units instead of in perce...

Page 51: ...Range bEFr The functions listed at Note are calculated before to apply the action selected by C Cn Main control output conditioning C F06 parameter AFtr The functions listed at Note are calculated af...

Page 52: ...c For more details see also NOTE about output conditioning at page 43 Secondary control output in engineering unit C F13 This parameter will be available only when secondary control output is configur...

Page 53: ...Note are calculated before to apply the action selected by SC Cn Secondary control output conditioning C F12 parameter AFtr The functions listed at Note are calculated after to apply the action select...

Page 54: ...when at least one control output is configured Range dIS Manual function disabled Enb Manual function may be enabled Output value for AUTO to MAN transfer C G04 This parameter will be available only...

Page 55: ...balanceless transfer the operative set point is aligned to the measure value NOTES 1 The alignment is not performed if measure is in error condition or Remote Set point is selected 2 The selected loc...

Page 56: ...safety value standard setting see chapter ERROR MESSAGES Cnd A When the instrument detects an overrange or underrange condition of the main input the servomotor is driven to its high limit position C...

Page 57: ...unction Stop sampling when logic level is 1 rSt Input contact used to reset acknowledge alarm Reset when logic level is 1 rE dr Input contact used for Reverse Direct control action selection Direct wh...

Page 58: ...P1 2 Input contact used for SP SP2 set point selection see note 2 SP3 4 Input contact used for SP3 SP4 set point selection see note 2 SP L r Input contact used for Local Remote set point selection Rem...

Page 59: ...level is 1 Au A Input contact used for Auto Manual selection Manual when logic level is 1 O LI Input contact used for output limiter activation Output limited when logic level is 1 Hold Input contact...

Page 60: ...level 1 when remote set point is used Event 1 contact status C H08 This parameter will be available only when OUT 1 is configured as event annunciator O1 Fn C E01 is equal to Eun 1 Range CLSd The outp...

Page 61: ...tion C H11 This parameter will be available only when OUT 3 is configured as event annunciator O3 Fn C E03 is equal to Eun 3 Range In E Error condition Over Under Open Shrt on main input Logic level 1...

Page 62: ...curs Cj Er Error condition on CJ measurement Logic level 1 when error occurs A In E Error condition Over Under Open on auxiliary input Logic level 1 when error occurs EA E Error condition on any measu...

Page 63: ...ONFIGURATION GROUP 6 C Ixx OTHERS CONFIGURATION PARAMETERS Green bargraph function C I01 This parameter will be available for MKC models only Range Pr Ur the green bargraph will show the process varia...

Page 64: ...lue C d05 to In H Read out full scale value C d06 Resolution of the deviation bargraph C I05 This parameter will be available only for MKC models when G brG C I01 is equal to DEV Range 1 2 5 10 20 or...

Page 65: ...nt will reach the respective limit and than it will maintain the output relay in open condition n bAL When PID value is higher than Main control output high limit r E05 or Secondary control output hig...

Page 66: ...Fd Fn to C OF when the load under test is energized during the OFF status of the main output relay de energized or SSR output status 0 SC On Set Fd Fn to SC On when the load under test is energized du...

Page 67: ...re detection alarm is signalled on OUT 4 NOTE Out failure detection alarm annunciator cannot be assigned to an output just configured as control output CONFIGURATION GROUP 7 C Lxx INPUT OUTPUT TEST Th...

Page 68: ...ized OFF Output disabled relay deenergized NOTE By pushing the s or t key it is possible to change the output state The setting above described is the same for the remaining outputs C L03 Digital inpu...

Page 69: ...GURATION This group will be displayed only when configuration modify mode is enabled Range nO with this selection the instrument comes back to the first display of the configuration modify mode YES th...

Page 70: ...with the configured output type the control output can be displayed in the following ways a 1 If the device is configured with servomotor control drive only the feedback position value is displayed i...

Page 71: ...nstrument shows for this output the feedback position instead of the output in percent f Push FUNC push button again the lower display will show S followed by the SECONDARY control output value in the...

Page 72: ...is used 1 Lit when OUT 1 is used as control output and it is in ON condition or when Event 1 is at logic level 1 or when alarm 1 is in alarm state and acknowledged Flashes when alarm 1 is in alarm sta...

Page 73: ...ut is a servomotor type the bargraph will show the valve position instead of the power output the first or last LED s is flashing when the feedback position is out of range 0 100 On the left bargraph...

Page 74: ...ctuator The Display function paragraph describes how to show the two current values The fault condition is shown on the lower display by the Fd AL indication AL may be flashing or steady on in accorda...

Page 75: ...g s and t To come back to the AUTO mode depress MAN push button for more then 1 sec or toggle the logic input The transfer from AUTO to MANUAL is bumpless this function is not provided if an output va...

Page 76: ...board or in REMOTE functions and parameters are controlled via serial link The REMOTE status is signalled by the REM LED This instrument allows to modify the operative and configuration parameters via...

Page 77: ...button until S rt parameter is shown 3 push s or t and set the On indication on the middle display 4 push the FUNC push button The ST LED will turn on or flashing according to the selected algorithm W...

Page 78: ...n the middle display of the group The possible security status are Enb the parameters of this group are not protected and they may be modified inh the parameters of this group are ever protected and t...

Page 79: ...he eventual modification on the last displayed parameter will be lost NOTES 1 In the following pages we will describe all the parameter of the instrument but it will show only the parameters related w...

Page 80: ...one for SP3 SP4 selection Range from rL r E12 to rH r E13 Group 1 default data loading r A05 Range OFF No loading data ON Loading data Run time group 2 r bxx SMART ENABLE DISABLE SMART function r b01...

Page 81: ...his parameter is available when alarm 1 is configured as process deviation main power output or secondary power output alarm A1 tP rF 01 Proc or dEV or Ain or SECn Range in engineering units within th...

Page 82: ...g units within the span limits for process alarm from 1000 to 1000 digits for deviation alarm from 0 0 to 100 0 for control output alarms NOTE The span limits are configured by In L C d05 and In H C d...

Page 83: ...Range from 0 to 1000 digits high threshold used when the alarm 3 is a band alarm r C10 This parameter is available only when the alarm 3 is configured as band alarm A3 tP rF 09 bAnd Range from 0 to 10...

Page 84: ...sent and Fd Fn C I10 is equal to C On or C OF or SC On or SC OF Range from 0 to Fd HS C I12 NOTES 1 The device is in alarm status when the current measured during the ON status of the load is lower th...

Page 85: ...igits Alarm 2 hysteresis r C17 This parameter is available only when Out 2 is configured as alarm output O2 Fn C E02 ALr 2 Range from 1 to 200 digits Alarm 3 hysteresis r C18 This parameter is availab...

Page 86: ...ing with SMART algorithm the Pb value will be limited as selected by parameters Pb Hi r L02 and Pb Lo r L01 Hysteresis for ON OFF control r d02 This parameter is available when Pb r d01 0 On OFF contr...

Page 87: ...0 0 to 100 0 of the output when device is configured with only one control output from 100 0 to 100 0 of the output when device is configured with two control outputs split range excluded Relative se...

Page 88: ...ading data Run time group 5 r Exx AUXILIARY CONTROL PARAMETER Anti reset wind up r E01 This parameter is available when at least one control output is configured and Pb r d01 is different from 0 Range...

Page 89: ...et by A UL C G04 parameter Main output cycle time r E07 This parameter is available when time proportional main control output is configured Range from 1 to 200 s Servo motor dead band r E03 This para...

Page 90: ...ay shows Inf meaning that no limit is imposed NOTES 1 This parameter will be active even if device is configured for On OFF control 2 During the transfer from AUTO to MANUAL if this action is programm...

Page 91: ...ll be a step change Rate of change for negative set point variations r E15 Range from 1 to 200 digits per minutes Above this value the display shows Inf and the transfer will be a step change Time out...

Page 92: ...ection and A I A C d14 is equal to nor Range On the local remote set point selection is made by external contact only OFF the local remote selection is made by RSP push button or serial link only Exte...

Page 93: ...forced to its default value and alarm status will be cleared Alarm 1 configuration r F02 This parameter is available only when OUT 1 is configured as alarm 1 output O1 Fn C E01 ALr 1 Range H A High al...

Page 94: ...function masks the alarm condition at instrument start up until process variable reaches the alarm threshold plus or minus hysteresis 2 The change from On to OFF has immediate effect while the change...

Page 95: ...function r F08 This parameter is available only when OUT 2 is configured as alarm 2 output O2 Fn C E02 ALr 2 Range OFF Stand by function disabled On Stand by function enabled NOTES 1 If the alarm is...

Page 96: ...ed as alarm 3 output O3 Fn C E03 ALr 3 Range H A High alarm outside band with automatic reset L A Low alarm inside band with automatic reset H A Ac High alarm outside band with automatic reset and ack...

Page 97: ...e change from OFF to On has effect at the next start up or set point change Alarm 4 type r F13 This parameter is available only when OUT 4 is configured as alarm 4 output O4 Fn C E04 ALr 4 Range Proc...

Page 98: ...igured as alarm 4 output O4 Fn C E04 ALr 4 Range OFF Stand by function disabled On Stand by function enabled NOTES 1 If the alarm is programmed as band or deviation alarm this function masks the alarm...

Page 99: ...lable only when one output is configured as OFD alarm annunciator Fd Fn C I11 equal to C On or C OF or SC On or SC OF and Fd Ou C I13 is different from nonE Range dir direct action Relay energized or...

Page 100: ...G01 is different from OFF Range from 1 to 255 Serial link baud rate r G03 This parameter is available only when S L Pr r G01 is different from OFF Range from 600 to 19200 baud 19200 baud is shown on d...

Page 101: ...feedback potentiometer calibration procedure Servomotor low limit positioning r H02 This parameter is available only when feedback potentiometer calibration enabling r H01 is equal to On Range 0 0 to...

Page 102: ...l to ON Range OFF To skip calibration and hold the previous value select OFF and then push FUNC On To memorize the current position as feedback high limit calibration select On and then push FUNC This...

Page 103: ...gized On Relay energized For OUT 11 up to OUT 19 the instrument will show on the lower display the related output and it is possible to perform the same setting as above described R I02 All relays dee...

Page 104: ...group 8 will be forced to their default values Run time group Hd r Lxx HIDDEN PARAMETERS SMART LIMITS NOTE This group is accessible from every group by keeping depress the MENU key for 8 secs Minimum...

Page 105: ...ured S Fn C G01 Enb Range from 00 01 mm ss to ti Hi r L04 Maximum value of integral time calculated by SMART algorithm r L04 This parameter is available only when smart function is configured S Fn C G...

Page 106: ...in input OVERRANGE or UNDERRANGE or SENSOR LEADS BREAK When the process variable exceeds the full scale value programmed by In t C d02 an OVERRANGE condition will be shown on the upper display as show...

Page 107: ...puts the Main output is forced to 100 and Secondary output is forced to 0 b With SF Cn C G07 set to Ov Un when an overrange or an underrange condition is detected the power output is forced to the saf...

Page 108: ...the control output as the complement of effect described at point a These instruments are capable to detect on the main input the sensor leads break condition When the sensor leads break condition is...

Page 109: ...n 4 20 mA or 1 5 V or 2 10 V NOTES 1 The fault conditions on the auxiliary input will be displayed only if the relative indication has been selected see Display function at page 62 2 When a fault cond...

Page 110: ...re Repeat the above described procedure if another error is shown Feedback potentiometer adjustment error If this error is detected span less than 20 of complete potentiometer travel push any key to l...

Page 111: ...rror may be generated by an ambient temperature higher than 70 C 158 F or lower than 20 C 4 F When one of these errors is detected contact your supplier Two errors related with the preliminary hardwar...

Page 112: ...V AC 50 60 Hz 15 to 10 of the nominal value 24 V AC DC 10 of the nominal value Power consumption 15 VA max for PKC model 16 VA max for MKC model Isolation voltage 2600 V rms according to IEC 1010 1 D...

Page 113: ...imum error 0 1 of span Cold junction automatic compensation from 0 to 50 C Cold junction accuracy 0 1 C C Input impedance 1 MW Calibration according to IEC 584 1 and DIN 43710 1977 T C type L J K T U...

Page 114: ...F selectable Measuring current 140 mA typical Line resistance automatic compensation up to 20 W wire with no measurable error 200 850 C 330 1560 F Input type RTD Pt 100 W IEC 751 Ranges 15 30 Input t...

Page 115: ...Reverse direct control action Input type Contact closure voltage free Active logic level Close or open programmable CURRENT TRANSFORMER INPUT FOR OUT FAILURE DETECTION The instruments equipped with t...

Page 116: ...for one control output from 0 to 100 of the output range for two control outputs split range excluded from 100 to 100 of the output range SET POINTS This instrument allows to use up to 4 set points S...

Page 117: ...possible to set output high limits output low limits output max rate of rise AUTO MANUAL mode selectable by front push button or logic input OUTPUTS Control output updating time 125 ms when a linear...

Page 118: ...otes 1 The commons of the out 3 and 4 are connected together with the same rear terminal 2 When OUT 3 and 4 are used as independent relay outputs the addition of the two currents must not exceed 3 A S...

Page 119: ...of the output 15 to 19 are connected with terminal 55 ALARMS Alarm action direct or reverse function programmable Alarm functions each alarm can be configured as process alarm band alarm deviation ala...

Page 120: ...to obtain an alarm condition when the secondary control output is lower or higher than a programmed value Operative mode Minimum or maximum programmable Threshold programmable from 0 1 to 100 0 of th...

Page 121: ...with one remote master unit MAINTENANCE 1 REMOVE POWER FROM THE POWER SUPPLY TERMI NALS AND FROM RELAY OUTPUT TERMINALS 2 Remove the instrument from case 3 Using a vacuum cleaner or a compressed air j...

Page 122: ...f the selected group The middle and lower display will show A 3 By s or t pushbuttons select the On indication on the central display A 4 Push the FUNC pushbutton The central display will show The def...

Page 123: ...AL2 Initial range value for process alarm 0 for deviation alarm 0 0 for control output alarm bA2 L 0 bA2 h 0 AL3 Initial range value for process alarm 0 for deviation alarm 0 0 for control output alar...

Page 124: ...Inf SC CY 15 s If relay output 2 s If SSR output rL Initial range value rH Final range value Grd1 Inf Grd2 Inf tOL Inf E A On E Lr On E rd On Run time group 6 r Fxx PARAMETER DEFAULT VALUE A1 tP Proc...

Page 125: ...is memorized in the instrument These data are the typical values loaded in the instrument prior to shipment from factory When it is desired to load the default value of all the configura tion paramete...

Page 126: ...in and select the Default configuration group C Cxx By s or t push button select the desired configuration parameter set tb 1 or tb 2 Push MENU pushbutton again The central display will show and then...

Page 127: ...s not mounted ALr 4 If option is mounted S tP CLSd If feedback circuitry is mounted OPEn If feedback circuitry is not mounted FEEd no Fb O5 Fn nonE If option is not mounted Ain If option is mounted O5...

Page 128: ...P1 2 d1 St CLSd d2 Fn SP3 4 d2 St CLSd d3 Fn rSt d3 St CLSd E1 Fn In E E1 St CLSd E2 Fn EA E E2 St CLSd E3 Fn Au A E3 St CLSd E4 Fn SP L r E4 St CLSd Configuration group 6 C Ixx PARAM VALUE NOTES G br...

Page 129: ...not mounted ALr 1 If servo motor drive or linear output are mounted O2 Fn ALr 2 O3 Fn nonE If option is not mounted C S If servo control motor drive is mounted ALr 3 If option is mounted O4 Fn nonE I...

Page 130: ...n nor S SCL nO SC dP No decimal figure SC E L 0 SC E H 100 SC A C bEFr Configuration group 4 C Gxx PARAM VALUE NOTES S Fn Enb Cn tP PId An F Enb A UL bu A t t bu St Fn Cnd b SF Cn Std SF UL 0 0 Config...

Page 131: ...NOTES G brG DEv O brG P Out brG L 150 F brG H 2500 F brG d 10 F SP AL n ALG SP dS OP SP Sr bH bAL SS tr 150 F t out t 10 Fd Fn nonE If option is not mounted or main control output is linear C On If o...

Page 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...

Page 133: ...3 CONFIGURATION 88 ALARM 3 STANDBY FUNCTION 89 ALARM 3 TYPE 88 ALARM 4 ACTION 90 ALARM 4 CONFIGURATION 89 ALARM 4 STANDBY FUNCTION 90 ALARM 4 TYPE 89 ALARM 1 THRESHOLD 73 ALARM 2 THRESHOLD 74 ALARM 3...

Page 134: ...ETPOINT VARIATION 83 RATE OF CHANGE FOR NEGATIVE SETPOINT VARIATION 83 Run time Menu hidden SMART LIMIT VALUE 95 ALARM 1 HYSTERESIS 77 ALARM 2 HYSTERESIS 77 ALARM 3 HYSTERESIS 77 ALARM 4 HYSTERESIS 77...

Page 135: ...RATE OF RISE 82 SECONDARY OUTPUT CYCLE TIME 82 SERVO MOTOR DEAD BAND 81 SERVO MOTOR TRAVEL TIME 80 Run time group 2 SMART ENABLE DISABLE 72 SMRT ENABLED OR DISABLED 72 MAIN SETPOINT 71 SETPOINT 2 71 S...

Page 136: ...CONTROL ACTION TYPE 47 LOGIC INPUT 1 FUNCTION 51 LOGIC INPUT 1 CONTACT STATUS 52 LOGIC INPUT 2 FUNCTION 52 LOGIC INPUT 2 CONTACT STATUS 53 LOGIC INPUT 3 FUNCTION 53 LOGIC INPUT 3 CONTACT STATUS 53 FI...

Page 137: ...ULL SCALE VALUE 44 MAIN OUTPUT INITIAL SCALE VALUE 44 MAIN CONTROL OUTPUT GAIN 42 ORANGE BARGRAPH FUNCTION 57 OUT 1 FUNCTION 36 OUT 2 FUNCTION 36 OUT 3 FUNCTION 37 OUT 4 FUNCTION 37 OUT 5 FILTER ON TH...

Page 138: ...ALE VALUE 46 SECONDARY CONTROL OUTPUT INITIAL SCALE VALUE 46 SECONDARY CONTROL OUTPUT GAIN 42 CONDITION FOR OUTPUT SAFETY VALUE 49 OUTPUT SAFETY VALUE 50 SMART FUNCTION 47 SERVOMOTOR TYPE 37 OPERATIVE...

Page 139: ...relay output 66 Two SSR outputs OUT3 and OUT4 0 Not provided 1 Two relay outputs 2 Two relay outputs interlockable by jumper for servomotor output OUT5 and OUT6 0 Not provided 5 Two mA outputs 7 One...

Page 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...

Page 141: ...Ero Electronic S r l Via E Mattei 21 28100Novara Italy Tel 390321481111 Fax 390321481112 E maileroelectronic ero eurotherm co uk Http www eroelectronic com Xkc Z C0 p65 5 29 02 12 01 PM 2...

Reviews: