© EPS Stromversorgung in 2022, this information is subject to change without notice
96
30000800_manual_psb_10000_4u_30kw_en_04
The fourth mode is called
Dynamic test
and combines
Static discharge
with
Static charge
in one flow. The same parame
-
ters for the single test parts are available, plus some extra for the flow. You can, for example, select what comes first, charge
or discharge. There is also an option to cycle the test, i. e. repeat 1 to 999 times or infinitely and you can define a resting
period which elapsed before the next cycle.
3.11.16.1 Settings for the static discharge mode
The following parameters can be configured for the
static discharge battery test function:
Value
Range
Description
Discharge current
0
...I
Nom
Maximum discharge current (in Ampere)
Power limitation
0
...P
Nom
Maximum discharge power (in Watt)
R mode
on/off
Enables the resistance mode for the test and unlocks the R value
Discharge resistance
R
Min
...R
Max
Maximum discharge resistance in Ω
3.11.16.2 Settings for the dynamic discharge mode
The following parameters can be configured for the
dynamic discharge battery test function:
Value
Range
Description
Discharge current 1
0
...I
Nom
Upper resp. lower current setting for pulsed operation (the higher value of
both is automatically used as upper level)
Discharge current 2
0
...I
Nom
Power limitation
0
...P
Nom
Maximum discharge power (in Watt)
Time t1
1...36000
s
t1 = Time for the upper level of the pulsed current (pulse)
t2 = Time for the lower level of the pulsed current (pause)
Time t2
1...36000
s
3.11.16.3 Settings for the static charge mode
The following parameters can be configured for the
static charge battery test function:
Value
Range
Description
Charge voltage
0
...U
Nom
Charging voltage (in Volt)
Charge current
0
...I
Nom
Maximum charging current (in Ampere)
Charge end current
0
...I
Nom
Current threshold (in Ampere) upon which the charging would stop
3.11.16.4 Settings for the dynamic test mode
The following parameters can be configured for the
dynamic test battery test function:
Value
Range
Description
Charge end current
0
...I
Nom
Threshold (in Ampere) upon which the charging part would stop
Charge voltage
0
...U
Nom
Charging voltage (in Volt)
Charge current
0
...I
Nom
Static charging current (in Ampere)
Charge time
1...36000 s
Duration of the charging part (max. 10 h)
Discharge end voltage
0
...U
Nom
Threshold (in Volt) upon which the discharging part would stop
Discharge current
0
...I
Nom
Static discharging current (in Ampere)
Discharge time
1...36000 s
Duration of the discharging part
Start with
Charge | Discharge
Determines whether the test starts with charging or discharging
Test cycles
0...65535
Number of cycles to run the complete test (0 = infinite cycles)
Rest time
1...36000 s
Time to rest the test before the next phase or cycle
3.11.16.5 Stop conditions
These parameters are valid for all test modes and define additionally stop conditions:
Value
Range
Description
Discharge end voltage
0
...U
Nom
Threshold (in Volt) to stop discharging (only for discharge modes)
Action: Ah limit
None, Signal, End of
test
Enables the optional stop condition