30
EN
Electrical installation must only be carried out by a qualified and licensed electrician.
The connections are made according to the connection diagram or according to the following
terminal diagrams
The generator has a pre-mounted power supply cable with a Cekon type plug (16A or 32A). For
connection the appropriate socket with fuse protection has to be used.
The control unit is connected as shown in the following connection diagrams. To simplify the in-
stallation, the connection terminals are colour coded and all individually numbered.
Anschlussklemmen und Sicherungen
für Leistungsanpassung, 18 kW
6.1 SteamRock II Basic 18kW
connection terminals
Terminal
Marking
Description
1
L1
L1 Phase
2
L1
(L4)
3
L2
L2 Phase
4
L2
(L5)
5
L3
L3 Phase
6
L3
(L6)
7-14
N
N
15-16
PE
PE power supply
16
PE
(PE power supply 2)
21
N1
N - control unit
22
S1
S1 - control unit
23
Wb
Steam on - control
24
PE
PE - control unit
25
ST1
Signal - output
26
ST2
Signal - output
27
Fragrance
Fragrance
28
PE
PE - Fragrance
Terminal diagram for SteamRock II Basic with 18 kW,
400 V connection (3 x 32 A).
Risk of electric shock
A faulty electrical connection poses the risk of an electric shock. This risk also applies
following completion of the installation work.
DANGER
6. Electrical installation