Commissioning
6.6 Defining the light source manually
The control panel is set to inductive loads by the factory so that resistive
loads can also be controlled by the control panel. If required, the light out-
put can also be manually set to capacitive loads.
If light bulbs are used, the load for lighting must remain as an inductive
load.
The current setting is shown on the display.
NOTICE
Material damage
Improper setup can damage the unit. In this case, the warranty be-
comes void.
Work must only be performed by a trained technician from an
authorised company specialised in the trade.
For this setting, the lighting must be disconnected.
Setting the load for lighting to resistive load
1
Disconnect the relay box from the power supply.
2
Open the relay box’s housing.
See
3
DANGER! Ensure that the relay box is disconnected from the power sup-
ply.
Disconnect the light source from the main circuit board.
4
Reconnect the power supply and switch on the relay box again.
Display symbol Setting
Code
Inductive/resistive load (lighting for phase con-
trol),
if light bulbs are used.
Factory setting
8001
Capacitive load (lighting for phase control)
Electrical ballasts for phase-cut dimmer
8002
R,L
R,C