14
Changing group of parameters
a Disconnect batteries if any.
b Disconnect the electrical power contact.
c Press the LEARN BUTTON (LRN) and keep it depressed.
d Connect the electrical power contact.
e Watch the ERROR LED.
3 s
5 s
1 s
f
Release the LEARN BUTTON after the 5 seconds (LED is out).
The ERROR LED flashes a number of short flashes that corresponds to the parameter group
number (see table). After a short pause the LED will repeat the group number, and so on.
g Pushing the LEARN BUTTON once, increases the parameter group number. When the highest
parameter group number is reached it will start with number 1 (default) again.
h Push the button until you get the requested parameter group.
i
Disconnect the electrical power contact.
j
Next time the electrical power is connected, the operator will use the new group of parameters.
10
9
8
7
6
5
4
3
2
1 (default)
Parameter/ Group
15 minutes
15 minutes
15 minutes
15 minutes
15 minutes
15 minutes
15 minutes
15 minutes
Infinite
15 minutes
OPEN/CLOSE
HOLD OPEN TIME
Convenience
Power Save
Power Save
Power Save
Power Save
Power Save
Power Save
Convenience
Power Save
Power Save
BATTERY mode
Locked dur-
ing KILL
Lock follows
program se-
lector during
KILL
Locked dur-
ing KILL
Locked dur-
ing KILL
Locked dur-
ing KILL
Locked dur-
ing KILL
Lock follows
program se-
lector during
KILL
Locked during
KILL
Locked dur-
ing KILL
Locked dur-
ing KILL
KILL mode
Reverses
when ob-
structed
Door closer
Door closer
Door closer
Door closer
Reverses
when ob-
structed
Door closer
Door closer
Door closer
Door closer
OBSTRUCTION
mode
1)
Separate
presence de-
tection
Separate pres-
ence detec-
tion
Separate
presence de-
tection
Separate
presence de-
tection
Common
presence de-
tection
Separate
presence de-
tection
Separate
presence de-
tection
Separate pres-
ence detec-
tion
Separate
presence de-
tection
Separate
presence de-
tection
DOUBLE EGRESS
mode
On
On
On
Off
On
On
On
On
On
On
LOCK RETRY
In AUTO
mode
In AUTO
mode
In OFF, EXIT
and AUTO
mode
In AUTO
mode
In AUTO
mode
In AUTO
mode
In AUTO
mode
In AUTO
mode
In AUTO
mode
In AUTO
mode
OPEN/CLOSE im-
pulse
Normally
Open
Normally
Closed
Normally
Open
Normally
Open
Normally
Open
Normally
Open
Normally
Open
Normally
Open
Normally
Open
Normally
Open
KILL Impulse
Configuration
1)
If set to REVERSES WHEN OBSTRUCTED, the operator re-opens when obstructed, similar to a presence impulse.
As default the operator tries to close two times extra in automatic operation, OFF or EXIT mode and one time in manual operation, OFF or
EXIT mode if there is a problem with binding striking plates. This function can be switched off (see LOCK RETRY above).
Note! When changing group of parameters, normally only the master control must be configured in a double door application. When
changing from or to group seven, both MASTER and SLAVE must be configured.
1005088-EMEI-11.0
Issue 2014-11-24
62
14 Changing group of parameters