Settings for double doors
Settings on the
Function
SLAVE
MASTER
Common
X
Program selection
X
Opening time
X
Closing time
X
Hold open time
X
Close / Continue to open when the door is obstructed
X
PAG On/Off
(X)*
X
Level of Power assist
(X)*
X
Extended closing force
X
OPD Impulse or Mat Logic Impulse
X
Selection of operating mode during operation on battery
power
Individual
X
X
Lock/Unlock signal voltage
X
X
Locked without/with power
X
X
Lock release Enable/Disable
X
X
Open Delay Time
X
X
Lock kick Enable/Disable
* For “Double egress doors”, these functions must be set separately for MASTER and SLAVE as the
arm systems as well as the air pressure may be different.
Note!
• Locks on the MASTER and SLAVE doors must be connected to the control unit (CU) on the cor-
responding operator.
• Inner and outer impulses can be connected to either MASTER or SLAVE CU or both.
• The OPD is to be connected to the MASTER CU except for “Double egress”, where each OPD
must be connected to corresponding CU.
• Door leaf mounted sensors must always be connected to corresponding CU.
• The slave door can be prevented to open, if kill is activated on the SLAVE control unit.
1005088-EMEI-11.0
Issue 2014-11-24
22