Default programming (00÷01)
Default programming sets the parameters to the factory
default values.
00
= Off (It is not possible to perform a default programming
from the MMI).
01
= On (It is possible to perform a default programming
from the MMI).
Learn (00÷01)
Sets the possibility to performa learn cycle..
00
= Off (It is not possible to perform a learn cycle from MMI).
01
= On (It is possible to perform a learn cycle from MMI).
AutoWidth (00÷01)
If this function is selected (01) and the operation mode
selection is AUTO PARTIAL. The door will open from partial
open width to full open width, if an opening impulse is given
and the door has not closed during the time selected in
parameter 22 “Auto Width Activation Time”.
00
= Off.
01
= On.
Power Supply Type (00÷02)
00
= DO NOT USE.
01
= 150W.
02
= 75W.
AUTOMATIC
Sustainable Drive Mode (00÷01)
The electromechanical lock will never lock in Exit mode
selection even if parameter 44 is set to On (01). The (+) 24 V
DC to accessories like sensors is turned off when the mode
selector is in Off and the door is closed. Motor power is
limited to 75Weven if parameter 71 is set to a higher value.
00
= Off.
01
= On.
Door Type (00÷01)
00
= single sliding.
01
= biparting.
TO BE SET
Door weight (00÷40kg x10)
Will be estimated during the Learn but can also be altered
manually.
NOTE
: The weight of the door is not automatically learned
on the DAS200RF, it must be set manually.
AUTOMATIC
(not on
DAS200RF)
Friction (00÷99N)
The friction when moving the door is automatically measu-
red during a Learn.
NOTE
: DAS200 not more than di 50N.
NOTE
: DAS200HD/RF/RG not more than 70N.
AUTOMATIC
Interlock Function (00÷01)
FUTURE USE
Synchronizing Function (00÷01)
FUTURE USE
External Bus Device ID (00÷99)
FUTURE USE