40
IP2266EN
EN
Convenience battery 24V, DAS902BAT2 (00÷01)
When this parameter is set to On (01), with a 24V (UPS)
battery the operator will continue its normal operation in
case of mains power failure (flat batteries: last operation=
opening). Monitoring will be made if parameter 10 is set to
Convenience Monitoring (01).
Not approved in escape routes!
00
= Off.
01
= On.
*NOTE
: on DAS200RG this display is not visible and is set to 00.
*NOTE
: on DAS200RF set to 00.
Emergency Unit Test Interval (04÷23hours)
The time set in this parameter controls the maximum
time until the next automatic test of the emergency unit
is performed.
Battery Type (00÷02)
What type of battery that is mounted in the operator is
identified during the Learn.
00
= No battery.
01
= 12V.
02
= 24V.
AUTOMATIC
Opening Delay For Lock (00÷99s x0,1)
The time the opening is delayed (0.0-9.9 sec) after an
opening impulse is given in operation mode selections
OFF and EXIT.
Exit Lock (00÷01)
This parameter controls the electromechanical lock in the
operation mode selector setting EXIT.
00
= Off. The electromechanical lock is not locked in EXIT.
01
= On. The electromechanical lock is locked in EXIT.
NOTE
: on DAS200RG this display is not visible and is set to 00.
NOTE
: on DAS200RF set to 00.
Stop Function (00÷01)
When this parameter is set to On (01) the Stop impulse is
enabled, otherwise it is disabled.
00
= Off.
01
= On.
Stop Configuration (00÷01)
00
= N.O.
01
= N.C.
Opening Max Force (02÷23N x10)
The force applied from the operator to the door leaf during
opening.
If the reopening maneuver occurs too abruptly, set para-
meter 49 with a value lower than the factory value (10),
example 04 - 05.
Close Kick Force (00÷23N x10)
The force applied from the operator to the door leaf during
the close kick.
Closing Max Force (02÷23N x10)
The force applied from the operator to the door leaf during
closing.