17
Installation instructions
EN
ELECTRICAL CONNECTIONS
DANGER
DANGER:
Only an authorized electrician
is allowed to perform electrical work on the
ventilation units.
Refer to the electrical drawings at the end of this
manual.
Preparing for electrical
installations
Before you start the installation, make sure that:
•
Appropriate power supply is available for the
ventilation unit.
•
At least 30 mA fault current protection is installed.
•
Because of this, no other electrical appliances
should be plugged into the same outlet.
•
There is appropriate cabling between the unit and
the control panel wall mount.
•
The cable must run inside a protective conduit
of at least Ø 20 mm.
•
The cable included in the basic delivery is
10 m. Optionally a 30 m cable is available.
•
The cable heads are type RJ4P4C.
eWind card connections
eWind card connections
NTC sensors
Input
Use
TE01
Outdoor temperature measuring TE01.
TE05
Supply air temperature after-heat recovery TE05.
TE10
Supply air temperature TE10
TE32
Exhaust air temperature TE32
TE02
Pre-heated outside air temperature TE02 (CHG/
AGH)
TE45
Return water temperature TE45 (W)
Return water temperature TE46 Option (CG).
Analog inputs AI 0-10V
Analog input AI1 for voltage range 0-10V
Functionality of this input is decided by user. (Parameter
c27)
Input
Use
AI1
External CO2 or %RH transmitter
Analog inputs AI7 - AI8 for voltage range 0-5V
Functionality of these inputs are locked by software.
AI7
Extract air humidity RH30
AI8
Extract air temperature TE30
eWind card connections
Analog Outputs AO 0 - 10V
Output Use
AO1
Control voltage for supply fan
AO2
Control voltage for extract fan
AO4
Control voltage for HRW
AO5
Control voltage for heating
AO6
Control voltage for electrical pre-heater. Control
voltage for (CHG). Control voltage for cooler (CG)
Digital outputs DO relays, potential free normally open
contacts.
Output Use
DO2
ON/OFF Control for heating
DO5
ON/OFF Control for dampers
DO8
A/AB alarm output NO (Default)
ON/OFF control for pre-heating (optional)
ON/OFF control for cooling (CG/CHG/AGH)
(optional)
Digital inputs DI (buttons and indications).
Connection to GND only! No voltage allowed to be
connected to digital inputs.
Input
Use
DI1
Emergency stop
DI2
External electrical after-heater or pre-heater alarm
DI4
Manual boost
DI5
Away mode. Away mode is active as long as the
input is grounded.
DI6
Fireplace/extractor hood mode. The fireplace
switch is a momentary push-button switch.
Fireplace mode is active 10 minutes from when
input is grounded. If connected to a changeover
switch, the circuit must be cut for the mode to
reactivate. The extractor hood mode is active
as long as the input is grounded. The selection
between fireplace mode or extractor hood mode
is done in parameter c12.
DI11
Supply fan tacho input
DI12
Extract fan tacho input
Miscellaneous connections
OP1,
OP2
Operating panel connections for eWind
X26
ModBus RTU
24VDC
+24VDC
GND
GND
Summary of Contents for eWind LTR-2
Page 1: ...12 7 2017 Enervent eWind Installation instruction ENG...
Page 48: ...48 Dimensional drawings Pinion right hand...
Page 49: ...49 Installation instructions EN Pinion left hand...
Page 50: ...50 Pingvin right hand...
Page 51: ...51 Installation instructions EN Pingvin left hand...
Page 52: ...52 Pingvin XL right hand...
Page 53: ...53 Installation instructions EN Pingvin XL left hand...
Page 54: ...54 Pandion...
Page 55: ...55 Installation instructions EN Pelican...
Page 56: ...56 Pegasos...
Page 57: ...57 Installation instructions EN LTR 2...
Page 58: ...58 LTR 3...
Page 59: ...59 Installation instructions EN LTR 4...
Page 60: ...60 LTR 6 25 mm...
Page 61: ...61 Installation instructions EN LTR 6 50 mm...
Page 62: ...62 LTR 7...
Page 63: ...63 Installation instructions EN Wiring digrams eWind basic wiring diagram...
Page 64: ...64 eWind basic wiring diagram Pingvin XL Pegasos and LTR 7...
Page 65: ...65 Installation instructions EN eWind basic external connections...
Page 66: ...66 eWind basic internal connections...
Page 67: ...67 Installation instructions EN eWind electrical heater 2kW...
Page 68: ...68 eWind electrical heater 2kW...
Page 69: ...69 Installation instructions EN eWind external electrical heater...
Page 70: ...70 eWind electrical pre heater...
Page 71: ...71 Installation instructions EN eWind extractor hood connections...
Page 72: ...72 Principal diagrams eWind HW principle scheme ESW_PRINCIPLE_SCHEME dwg...
Page 73: ...73 Installation instructions EN eWind CG principle scheme 1...
Page 74: ...74 eWind CG principle scheme 2...
Page 75: ...75 Installation instructions EN eWind CG principle scheme 3...
Page 76: ...76 eWind CG principle scheme 4...
Page 77: ...77 Installation instructions EN eWind CG principle scheme 5...
Page 78: ...78 eWind CG connections...
Page 80: ...80 eWind CHG principle scheme heat exchanger...
Page 81: ...81 Installation instructions EN eWind CW principle scheme...
Page 88: ...88 eWind CHG CHG eWind ELECTRICAL CABINET UNIT eWind_REV_A eWind CHG...
Page 93: ...93 Installation instructions EN...
Page 94: ...94...