40
Troubleshooting
Alarm
Description
Alarm
limit
Symptoms
Possible reason
Action
Notes
FILS
Service
reminder.
4 or 6
months
Time for regular
maintenance.
Change filters.
Inspect ventilation unit.
Clean as needed.
Look for damages.
Press any
button for 5
seconds to
acknowledge
Err
Sensor
malfunction.
A sensor is short- or open
circuited.
Check the connections
and wiring of sensors
- - - -
Downloading
eWind panel is
downloading data from
eWind main board.
Normal at start-up.
Otherwise check the
eWind connection cable.
oFFE
Stop mode.
Ventilation off.
Ventilation unit is
commanded to stop mode
by an external control
system.
AL1
Water heater
coil in danger
of freezing.
+8 °C
Supply air
cold.
Water coil has frozen / is
about to freeze:
• Circulation pump has
stopped.
• Heat exchanger is not
rotating.
• Actuator of the water coil’s
control valve is faulty.
• Extract fan has stopped.
Restart the pump.
Replace the motor or the
belt.
Replace the actuator.
Find out why / replace
the fan.
The unit will
not start before
the alarm
condition has
been removed
and the alarm
acknowledged
by pressing
any button on
the operating
panel.
AL2
Supply air
after HRW is
cold.
+5 °C
Supply air
cold.
Heat exchanger is not
rotating:
• Drive belt is broken.
• Drive belt is slipping.
• Heat exchanger motor has
broken down.
Replace the drive belt.
Clean or change the belt
and the heat exchanger.
Replace the heat
exchanger motor.
The ventilation
unit enters the
malfunction
status, which
means that
the fans are
at minimum
speed.
The alarm is
automatically
acknowledged
after the fault
condition is
removed.
AL3
Supply air
cold.
+10 °C
Supply air
cold.
Extract fan has stopped.
Replace the fan.
Extract filter is blocked.
Replace filter.
Ventilation is adjusted
incorrectly / not adjusted
at all.
Readjust/adjust
ventilation according
to the ventilation
system design, using
appropriate measuring
tools.
Heat insulation for the
ducts is inadequate.
Check the thickness of
the insulation in supply
and extract air ducts and
add insulation, if needed.
Ventilation unit fan speed is
incorrect.
Always use the fan
speed specified by
the ventilation system
designer (even in winter)
AL4
Supply fan
failure.
No Supply air.
Supply air fan has stopped.
Repair or change the
supply fan.
The unit will
not start before
the alarm
condition has
been removed
and the alarm
acknowledged
by pressing
any button on
the operating
panel.
AL5
Extract fan
failure.
No Extract air.
Extract air fan has stopped.
Repair or change the
extract fan
Summary of Contents for eWind LTR-2
Page 1: ...12 7 2017 Enervent eWind Installation instruction ENG...
Page 48: ...48 Dimensional drawings Pinion right hand...
Page 49: ...49 Installation instructions EN Pinion left hand...
Page 50: ...50 Pingvin right hand...
Page 51: ...51 Installation instructions EN Pingvin left hand...
Page 52: ...52 Pingvin XL right hand...
Page 53: ...53 Installation instructions EN Pingvin XL left hand...
Page 54: ...54 Pandion...
Page 55: ...55 Installation instructions EN Pelican...
Page 56: ...56 Pegasos...
Page 57: ...57 Installation instructions EN LTR 2...
Page 58: ...58 LTR 3...
Page 59: ...59 Installation instructions EN LTR 4...
Page 60: ...60 LTR 6 25 mm...
Page 61: ...61 Installation instructions EN LTR 6 50 mm...
Page 62: ...62 LTR 7...
Page 63: ...63 Installation instructions EN Wiring digrams eWind basic wiring diagram...
Page 64: ...64 eWind basic wiring diagram Pingvin XL Pegasos and LTR 7...
Page 65: ...65 Installation instructions EN eWind basic external connections...
Page 66: ...66 eWind basic internal connections...
Page 67: ...67 Installation instructions EN eWind electrical heater 2kW...
Page 68: ...68 eWind electrical heater 2kW...
Page 69: ...69 Installation instructions EN eWind external electrical heater...
Page 70: ...70 eWind electrical pre heater...
Page 71: ...71 Installation instructions EN eWind extractor hood connections...
Page 72: ...72 Principal diagrams eWind HW principle scheme ESW_PRINCIPLE_SCHEME dwg...
Page 73: ...73 Installation instructions EN eWind CG principle scheme 1...
Page 74: ...74 eWind CG principle scheme 2...
Page 75: ...75 Installation instructions EN eWind CG principle scheme 3...
Page 76: ...76 eWind CG principle scheme 4...
Page 77: ...77 Installation instructions EN eWind CG principle scheme 5...
Page 78: ...78 eWind CG connections...
Page 80: ...80 eWind CHG principle scheme heat exchanger...
Page 81: ...81 Installation instructions EN eWind CW principle scheme...
Page 88: ...88 eWind CHG CHG eWind ELECTRICAL CABINET UNIT eWind_REV_A eWind CHG...
Page 93: ...93 Installation instructions EN...
Page 94: ...94...