Appendix
Batch Controller RA33
74
Hauser
On error
220061-00 Configure what value the device should continue working
with (for calculations) if the measured value is not valid
(e.g. cable open circuit).
Error value
220062-00 Only if the setting "Error value" has been selected under
"On error".
The device continues calculating with this value in the
event of an error.
The calculated values are recorded in the deficit counter.
The normal counter remains unchanged (does not run).
Density
Settings for the temperature input.
Damping
220008-01 Factory setting: 0.0 s. The more unwanted interference is
superimposed over the measuring signal, the higher the
value should be set. Result: Fast changes are dampened/
suppressed.
Decimal number, max. 5 digits incl. decimal separator.
Meas.val. corrct.
Determines the correction values used to compensate for
measurement section tolerances.
Proceed as follows:
1.
Measure the current measured value at the lower
measuring range.
2.
Measure the current measured value at the upper
measuring range.
3.
Enter the upper and lower target value and actual
value.
Range start
Lower correction value
Target value
220052-01 Enter the lower setpoint here.
Decimal number, max. 8 digits including decimal separa-
tor.
Actual value
220053-01 Enter the lower value actually measured here.
Decimal number, max. 8 digits including decimal separa-
tor.
Meas. range end
Upper correction value
Target value
220055-01 Enter the upper setpoint here.
Decimal number, max. 8 digits including decimal separa-
tor.
Actual value
220056-01 Enter the upper value actually measured here.
Decimal number, max. 8 digits including decimal separa-
tor.
Fault mode
Settings that define how this channel is to react under
fault conditions (e.g. cable open circuit, over range).
NAMUR NE 43
220060-01 Switch on/off monitoring of the 4 to 20 mA range as per
NAMUR Recommendation NE 43.
The following fault ranges apply when NAMUR NE43 is
enabled:
•
≤
3.8 mA: Under range
•
≥
20.5 mA: Over range
•
≤
3.6 mA or
≥
21.0 mA: Sensor error
•
≤
2mA: Open circuit
On error
220061-01 Configure what value the device should continue working
with (for calculations) if the measured value is not valid
(e.g. cable open circuit).
Error value
220062-01 Only if the setting "Error value" has been selected under
"On error".
The device continues calculating with this value in the
event of an error.
The calculated values are recorded in the deficit counter.
The normal counter remains unchanged (does not run).