Appendix
Batch Controller RA33
66
Hauser
Density
Settings for the density input
Signal type
220000-01 Select the signal type for the density input.
Channel ident.
220002-01 Identifier for the density input. User-defined text, 6 char-
acters.
Unit
220003-01 Select the density unit.
Decimal point
220004-01 Select the number of decimal points that are used for the
density input.
Range start
220006-01 Configure what value corresponds to 0/4 mA.
Numerical value, max. 8 digits including decimal separa-
tor.
Meas. range end
220007-01 Configure what value corresponds to 20 mA.
Numerical value, max. 8 digits including decimal separa-
tor.
Digital 1/2
Setting up only required if the digital inputs (e.g. events)
are to be used.
Function
250000-00
250000-01
Select the desired function,
33. Digital inputs are
High active, i.e. the described effect takes place when acti-
vated with High.
Low = -3 to +5 V
High = +12 to +30 V
Outputs
Settings only needed if outputs (e.g. relay or analog out-
puts) should be used.
Universal output
Settings for the universal output (current or pulse output).
Signal type
310000-00 Select the output signal for this channel.
Channel/value
310001-00 Select which channel or calculated value is to be output at
the output.
Start Value
310003-00 Configure what value corresponds to 0/4 mA.
Numerical value, max. 8 digits including decimal separa-
tor.
Full scale value
310004-00 Configure what value corresponds to 20 mA.
Numerical value, max. 8 digits including decimal separa-
tor.
Damping
310005-00 Time constant of the first order low pass for the output sig-
nal. This is used to prevent large fluctuations in the output
signal (can only be selected for the signal type 0/4 to 20
mA).
Numerical value, max. 8 digits including decimal separa-
tor.
Current start value
310022-00 Current that should be output at the start of the batch.
Only for the setting "channel/value = curve".
Start max.
310020-00 Two points are defined for the actuator curve. This is the
percentage value to reach the 20 mA value.
Only for the setting "Channel/value =Curve".
Stop max.
310021-00 Two points are defined for the actuator curve. This is the
percentage value to move away from the 20 mA value.
Only for the "Channel/value =Curve" setting.
Pulse Value
310006-00 The pulse value specifies what quantity an output pulse
corresponds to (e.g. 1 pulse = 5 liters).
Numerical value, max. 8 digits including decimal separa-
tor.
Pulse width
310007-00 The pulse width limits the max. possible output frequency
of the pulse output. Define a fixed or dynamic pulse
width.