Troubleshooting
Batch Controller RA33
48
Hauser
• Invalid meas.val.
9.4
Output function test
In the Diagnostics/Simulation menu, the user can output certain signals at the outputs (function
text).
The simulation is ended automatically if the user has not pressed any buttons for 5 minutes or has
switched off the function explicitly.
Relay tests
The user can switch the relay manually.
Analog output
Allows you to output a current value for test purposes. You can configure fixed values:
• 3.6 mA
• 4.0 mA
• 8.0 mA
• 12.0 mA
• 16.0 mA
• 20.0 mA
• 20.5 mA
• 21.0 mA
Pulse outputs (Pulse / OC)
Allows you to output pulse packages for test purposes. The following frequencies are possible:
• 0.1 Hz
• 1 Hz
• 5 Hz
• 10 Hz
• 50 Hz
• 100 Hz
• 200 Hz
• 500 Hz
The following simulations are possible for the pulse output only
• 1 kHz
• 5 kHz
• 10 kHz
Status of the outputs
The current status of the relays and open collector outputs can be queried in the "Diagnostics/Out-
puts" menu (e.g. relay 1: open).